Each ground anchor must be manufactured and provided with installation instructions, in accordance with its listing or certification.A nationally recognized testing agency must list, or a registered professional engineer or registered architect must certify, the ground anchor for use in a classified soil (refer to Subchapter C, Section II), based on a nationally recognized testing protocol, or a registered professional engineer or registered architect must certify that the ground anchor is capable of resisting all loads in Paragraph B of this section for the soil type or classification.
Ground anchors must be installed in accordance with their listing or certification, be installed to their full depth, be provided with protection against weather deterioration and corrosion at least equivalent to that provided by a coating of zinc on steel of not less than 0.30 oz./ft2 of surface coated, and be capable of resisting a minimum ultimate load of 4,725 lbs, and a working load of 3,150 lbs, as installed, unless reduced capacities are noted in accordance with Note 11 of Table 1 to this section or Note 12 of Tables 2 and 3 to this section.The ultimate load and working load of ground anchors and anchoring equipment must be determined by a registered professional engineer or registered architect, or tested by a nationally recognized third-party testing agency in accordance with a nationally recognized testing protocol.
A 1 1/4 inch x 0.035 inch or larger steel strapping conforming to ASTM D 3953-97, Standard Specification for Strapping, Flat Steel and Seals (incorporated by reference), Type 1, Grade 1, Finish B, with a minimum total capacity of 4,725 lbs and a working capacity of 3,150 lbs must be used.The tie-down straps must be provided with protection against weather deterioration and corrosion at least equivalent to that provided by a coating of zinc on steel of not less than 0.30 oz./ft2 of surface coated.Slit or cut edges of coating strapping need not be zinc coated.
Manufactured homes must also be stabilized against wind in the longitudinal direction in all Wind Zones.Manufactured homes located in Wind Zones II and III must have longitudinal ground anchors installed on the ends of the manufactured home transportable section(s) or be provided with alternative systems that are capable of resisting wind forces in the longitudinal direction.See Figure C to Subchapter E, Section II for an example of one method that may be used to provide longitudinal anchoring.A registered professional engineer or registered architect must certify the longitudinal anchoring method or any alternative system used as adequate to provide the required stabilization, in accordance with acceptable engineering practice.
Figure A to Subchapter E, Section II - Ground Anchor Installations
Ground Anchor Locations and Spacing (Plan View)
Notes to Figure A:
Figure B to Subchapter E, Section II - Ground Anchor Installation
Anchor Strap and Pier Relationship
Notes to Figure B:
Figure C to Subchapter E, Section II - Ground Anchor Installation
Longitudinal Anchoring
Table 1 to Subchapter E, Section II - Ground Anchor Installation
Maximum Diagonal Tie-down Strap Spacing
Wind Zone I
Nominal floor width, single section/multi-section | Max. height from ground to diagonal strap attachment | I-beam spacing 82.5 in. | I-beam spacing 99.5 in. |
12/24 ft. 144 in. nominal section(s) ........................ | 25 in ................................... 33 in ................................... 46 in ................................... 67 in ................................... | 14 ft. 2 in ........................... 11 ft. 9 in ........................... 9 ft. 1 in ............................. N/A ..................................... | N/A N/A N/A N/A |
14/28 ft. 168 in. nominal section(s) ........................ | 25 in ................................... 33 in ................................... 46 in ................................... 67 in ................................... | 18 ft. 2 in ........................... 16 ft. 1 in ........................... 13 ft. 3 in ........................... 10 ft. 0 in ........................... | 15 ft. 11 in 13 ft. 6 in. 10 ft. 8 in. N/A |
16/32 ft. 180 in. to 192 in. nominal section(s) ......... | 25 in ................................... 33 in ................................... 46 in ................................... 67 in ................................... | N/A ..................................... 19 ft. 0 in ........................... 16 ft. 5 in ........................... 13 ft. 1 in ........................... | 19 ft. 5 in. 17 ft. 5 in. 14 ft. 7 in. 11 ft. 3 in. |
Notes to Table 1:
Table 2 to Subchapter E, Section II - Ground Anchor Installation
Maximum Diagonal Tie-down Strap Spacing
Wind Zone II
Nominal floor width, single section/multi-section | Max. height from ground to diagonal strap attachment | Near beam method I-beam spacing | Second beam method I-beam spacing | ||
82.5 in. | 99.5 in. | 82.5 in. | 99.5 in. | ||
12 ft./24 ft. 144 in. nominal section(s). | 25 in ............................ | 6 ft. 2in ................ | 4 ft. 3 in ........... | N/A ...... | N/A |
33 in ............................. | 5 ft. 2in ................ | N/A ................... | N/A ...... | N/A | |
46 in ............................. | 4 ft. 0 in .............. | N/A ................... | N/A ...... | N/A | |
67 in ............................. | N/A ....................... | N/A .................... | 6 ft. 1 in .. | 6 ft. 3 in | |
14 ft./28 ft. 168 in. nominal section(s). | 25 in .............................. | 7 ft. 7in.................. | 6 ft. 9in ............. | N/A ...... | N/A |
33 in .............................. | 6 ft. 10in .............. | 5 ft. 9 in ............. | N/A ...... | N/A | |
46 in .............................. | 5 ft. 7in ................ | 4 ft. 6 in............ | N/A ...... | N/A | |
67 in .............................. | 4 ft. 3 in .............. | N/A .................... | N/A ...... | N/A | |
16 ft./32 ft. 180 in. to 192 in. nominal section(s). | 25 in .............................. | N/A ....................... | 7 ft. 10in ........... | N/A ...... | N/A |
33 in ............................. | 7 ft. 6in ................ | 7 ft. 2in ............. | N/A ...... | N/A | |
46 in .............................. | 6 ft. 9in ................ | 6 ft. 0 in ............. | N/A ...... | N/A | |
67 in ............................. | 5 ft. 4in ................ | ....................... 4 ft. 7 in ............ | N/A ....... | N/A |
Notes to Table 2:
Table 3 to Subchapter E, Section II - Ground Anchor Installation
Maximum Diagonal Tie-down Strap Spacing
Wind Zone III
Nominal floor width, single section/multi-section | Max. height from ground to diagonal strap attachment | Near beam method I-beam spacing | Second beam method I-beam spacing | ||
82.5 in. | 99.5 in. | 82.5 in. | 99.5 in. | ||
12 ft/24 ft. 144 in.nominal section(s). | 25 in ........................ | 5 ft.1 in ............. | N/A ................. | N/A ........... | N/A |
33 in ......................... 46 in ......................... 67 in ......................... | 4 ft.3 in ............. N/A ..................... N/A ..................... | N/A ................. N/A ................. N/A ................. | N/A ............ N/A ........... N/A ............ | N/A N/A N/A | |
14 ft/28 ft. 168 in. nominal section(s). | 25 in ........................ | 6 ft. 2 in ............. | 5 ft. 7 in ........... | N/A ............ | N/A |
33 in ........................ | 5 ft. 8 in ............. | 4 ft. 9 in ........... | N/A ............ | N/A | |
46 in ........................ | 4 ft. 8 in ................ | N/A ................. | N/A ............ | N/A | |
67 in ......................... | N/A .................... | N/A ................. | N/A ........... | N/A | |
16 ft/32 ft. 180 in. to 192 in. nominal section(s). | 25 in ......................... | N/A .................... | 6ft. 3 in ............. | N/A ............ | N/A |
33 in ......................... | 6 ft. 1 in ............ | 5 ft. 11 in .......... | N/A ............ | N/A | |
46 in ......................... | 5 ft. 7 in ............. | 5 ft. 0 in ............ | N/A ............ | N/A | |
67 in ......................... | 4 ft.5 in ............. | N/A ................ | N/A ............ | N/A |
Notes to Table 3:
02-385 C.M.R. ch. 890, § E-II