Section 385-890-D-XI - Required Perimeter SupportsA. Perimeter pier or other supports must be located as follows: 1. On both sides of side wall exterior doors (such as entry, patio, and sliding glass doors) and any other side wall openings of 48 inches or greater in width, and under load-bearing porch posts, factory installed fireplaces, and fireplace stoves.)2. Other perimeter supports must be: a. Located in accordance with Table 2 to Subchapter D, Section III; orb. Provided by other means such as additional outriggers or floor joists.When this alternative is used, the design required by Subchapter D, Section I must consider the additional loads in sizing the pier and footing supports under the main chassis beam.B. For roof live loads of 40 psf or greater, a professional registered engineer or professional architect must determine the maximum sidewall opening permitted without perimeter pier or other supports.C. The location and installation of any perimeter pier support must not take the home out of compliance with the Manufactured Home Construction and Safety Standards (part 3280).02-385 C.M.R. ch. 890, § D-XI