La. Admin. Code tit. 55 § V-5047

Current through Register Vol. 50, No. 11, November 20, 2024
Section V-5047 - Feed Water Connections
A. Feed water, makeup water, or water treatment shall be introduced into a boiler through the return piping system. Alternatively, makeup water or water treatment may be introduced through an independent connection. The water flow from the independent connection shall not discharge directly against parts of the boiler exposed to direct radiant heat from the fire. Makeup water or water treatment shall not be introduced through openings or connections provided inspection or cleaning, safety valve, safety relief valve, blow off, water column, water gage glass, pressure gage, or temperature.
B. The makeup water pipe shall be provided with a check valve near the boiler and a stop valve or cock between the check valve and the boiler or between the check valve and the return pipe system.

La. Admin. Code tit. 55, § V-5047

Promulgated by the Department of Public Safety, Office of the State Fire Marshal, LR 33:1363 (July 2007).
AUTHORITY NOTE: Promulgated in accordance with R.S. 23:531 and R.S. 51:1424.