Section V-3155 - Plan Review
A. No fire sprinkler system/equipment requiring plan submittal in accordance with R.S. 40:1574 et seq., shall be installed prior to submitting plans with required documentation and receiving authorization to install such system from the Plan Review Section of the Office of the State Fire Marshal. However, the installation of piping only shall be permitted upon receipt of plans and the issuance of a project number by the Office of the State Fire Marshal, Plan Review Section. No control valves shall be installed prior to review or written authorization by the Office of the State Fire Marshal. Any required changes determined by the review shall be the responsibility of the contractor.
B. All submittals for plan review shall identify the licensed firm performing the installation and responsible qualifier.
C. Only listed qualifiers of a firm shall be listed on applications for plan review or exemption forms to plan review. Additionally, any correspondence regarding a submittal, to include but not be limited to, telephone, email or written correspondence, shall only be through a listed qualifier of the firm, owner of the firm, a professional of record or owner of the building.
D. A new plan review shall be required when a firm takes over a project from another firm, listing the new firm's information and any changes to the project.

La. Admin. Code tit. 55, § V-3155

Promulgated by the Department of Public Safety and Corrections, Office of State Fire Marshal, LR 35:687 (April 2009).
AUTHORITY NOTE: Promulgated in accordance with R.S. 40:1664.2 et seq.