Section XIV-917 - Vents for Fixture Trap below Trap Weir/Fixtures Entering at Different LevelsA. Hydraulic Gradient. Fixture drains shall be vented within the hydraulic gradient between the top weir of the trap's outlet and the internal opening of the vent connection, but in no case shall the unvented drain exceed the distance provided for in Table 913.A of this code. See §913. C of this code.B. Different Levels. If any single branch interval has fixtures entering the stack at different vertical levels, the fixtures other than the fixture entering at the highest level shall be individually vented, except as may be otherwise permitted in other Sections of this Chapter. See §915. B C, and 925.C of this code.La. Admin. Code tit. 51, § XIV-917
Promulgated by the Department of Health and Hospitals, Office of Public Health, LR 38:2862 (November 2012).AUTHORITY NOTE: Promulgated in accordance with R.S. 40:4(A)(7) and R.S. 40:5(2)(3)(7)(9)(16)(17)(20).