La. Admin. Code tit. 46 § XL-311

Current through Register Vol. 50, No. 11, November 20, 2024
Section XL-311 - Structural Systems
A. The home inspector shall inspect structural components including:
1. foundation;
2. framing;
3. columns; and
4. piers.
B. The home inspector shall describe the type of:
1. foundation;
2. floor structure;
3. wall structure;
4. columns;
5. piers;
6. ceiling structure; and
7. roof structure.
C. The home inspector shall:
1. probe structural components only where deterioration is visible, except where probing would damage any surface;
2. enter readily accessible under floor crawl spaces, basements, and attic spaces and, if applicable, report the reason why an area was not readily accessible;
3. report the methods used to inspect or access under floor crawl spaces and attics; and
4. report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.

La. Admin. Code tit. 46, § XL-311

Promulgated by the Department of Economic Development, Board of Home Inspectors, LR 26:2747 (December 2000), amended by the Office of the Governor, Board of Home Inspectors, LR 30:1690 (August 2004), LR 41:923 (May 2015).
AUTHORITY NOTE: Promulgated in accordance with R.S. 37:1475.