Current through Register Vol. 50, No. 11, November 20, 2024
Section XIII-2931 - Compressor Stations: Inspection and Testing of Relief Devices [49 CFR 192.731]A. Except for rupture discs, each pressure relieving device in a compressor station must be inspected and tested in accordance with §2939 and 2943, and must be operated periodically to determine that it opens at the correct set pressure. [ 49 CFR 192.731(a)]B. Any defective or inadequate equipment found must be promptly repaired or replaced. [ 49 CFR 192.731(b)]C. Each remote control shutdown device must be inspected and tested at intervals not exceeding 15 months, but at least once each calendar year, to determine that it functions properly. [ 49 CFR 192.731(c)]La. Admin. Code tit. 43, § XIII-2931
Promulgated by the Department of Natural Resources, Office of Conservation, LR 9:246 (April 1983), amended LR 10:538 (July 1984), LR 30:1270 (June 2004).AUTHORITY NOTE: Promulgated in accordance with R.S. 30:501 et seq.