La. Admin. Code tit. 43 § XIII-2925

Current through Register Vol. 50, No. 11, November 20, 2024
Section XIII-2925 - Test Requirements for Reinstating Service Lines [49 CFR 192.725]
A. Except as provided in Subsection B of this Section, each disconnected service line must be tested in the same manner as a new service line, before being reinstated. [ 49 CFR 192.725(a)]
B. Each service line temporarily disconnected from the main must be tested from the point of disconnection to the service line valve in the same manner as a new service line, before reconnecting. However, if provisions are made to maintain continuous service, such as by installation of a bypass, any part of the original service line used to maintain continuous service need not be tested. [ 49 CFR 192.725(b)]

La. Admin. Code tit. 43, § XIII-2925

Promulgated by the Department of Natural Resources, Office of Conservation, LR 9:245 (April 1983), amended LR 10:538 (July 1984), LR 30:1269 (June 2004).
AUTHORITY NOTE: Promulgated in accordance with R.S. 30:501 et seq.