Section XIII-2721 - Maximum Allowable Operating Pressure: High-Pressure Distribution Systems [49 CFR 192.621]A. No person may operate a segment of a high pressure distribution system at a pressure that exceeds the lowest of the following pressures, as applicable: [ 49 CFR 192.621(a)] 1. the design pressure of the weakest element in the segment, determined in accordance with Chapter 9 and 11 of this Subpart; [ 49 CFR 192.621(a)(1)]2. 60 psi (414 kPa) gage, for a segment of a distribution system otherwise designated to operate at over 60 psi (414 kPa) gage, unless the service lines in the segment are equipped with service regulators or other pressure limiting devices in series that meet the requirements of §1157 C; [ 49 CFR 192.621(a)(2)]3. 25 psi (172 kPa) gage in segments of cast iron pipe in which there are unreinforced bell and spigot joints; [ 49 CFR 192.621(a)(3)]4. the pressure limits to which a joint could be subjected without the possibility of its parting; [ 49 CFR 192.621(a)(4)]5. the pressure determined by the operator to be the maximum safe pressure after considering the history of the segment, particularly known corrosion and the actual operating pressures. [ 49 CFR 192.621(a)(5)]B. No person may operate a segment of pipeline to which Paragraph A.5 of this Section applies, unless overpressure protective devices are installed on the segment in a manner that will prevent the maximum allowable operating pressure from being exceeded, in accordance with §1155 [ 49 CFR 192.621(b)]La. Admin. Code tit. 43, § XIII-2721
Promulgated by the Department of Natural Resources, Office of Conservation, LR 9:242 (April 1983), amended LR 10:535 (July 1984), LR 30:1264 (June 2004).AUTHORITY NOTE: Promulgated in accordance with R.S. 30:501 et seq.