La. Admin. Code tit. 43 § XIII-1141

Current through Register Vol. 50, No. 11, November 20, 2024
Section XIII-1141 - Distribution Line Valves [49 CFR 192.181]
A. Each high-pressure distribution system must have valves spaced so as to reduce the time to shut down a section of main in an emergency. The valve spacing is determined by the operating pressure, the size of the mains, and the local physical conditions. [ 49 CFR 192.181(a)]
B. Each regulator station controlling the flow or pressure of gas in a distribution system must have a valve installed on the inlet piping at a distance from the regulator station sufficient to permit the operation of the valve during an emergency that might preclude access to the station. [ 49 CFR 192.181(b)]
C. Each valve on a main installed for operating or emergency purposes must comply with the following. [ 49 CFR 192.181(c)]
1. The valve must be placed in a readily accessible location so as to facilitate its operation in an emergency. [ 49 CFR 192.181(c)(1)]
2. The operating stem or mechanism must be readily accessible. [ 49 CFR 192.181(c)(2)]
3. If the valve is installed in a buried box or enclosure, the box or enclosure must be installed so as to avoid transmitting external loads to the main. [ 49 CFR 192.181(c)(3)]

La. Admin. Code tit. 43, § XIII-1141

Promulgated by the Department of Natural Resources, Office of Conservation, LR 9:225 (April 1983), amended LR 10:518 (July 1984), LR 30:1237 (June 2004).
AUTHORITY NOTE: Promulgated in accordance with R.S. 30:501 et seq.