La. Admin. Code tit. 43 § XIII-1131

Current through Register Vol. 50, No. 11, November 20, 2024
Section XIII-1131 - Compressor Stations: Additional Safety Equipment [49 CFR 192.171]
A. Each compressor station must have adequate fire protection facilities. If fire pumps are a part of these facilities, their operation may not be affected by the emergency shutdown system. [ 49 CFR 192.171(a)]
B. Each compressor station prime mover, other than an electrical induction or synchronous motor, must have an automatic device to shut down the unit before the speed of either the prime mover or the driven unit exceeds a maximum safe speed. [ 49 CFR 192.171(b)]
C. Each compressor unit in a compressor station must have a shutdown or alarm device that operates in the event of inadequate cooling or lubrication of the unit. [ 49 CFR 192.171(c)]
D. Each compressor station gas engine that operates with pressure gas injection must be equipped so that stoppage of the engine automatically shuts off the fuel and vents the engine distribution manifold. [ 49 CFR 192.171(d)]
E. Each muffler for a gas engine in a compressor station must have vent slots or holes in the baffles of each compartment to prevent gas from being trapped in the muffler. [ 49 CFR 192.171(e)]

La. Admin. Code tit. 43, § XIII-1131

Promulgated by the Department of Natural Resources, Office of Conservation, LR 9:225 (April 1983), amended LR 10:517 (July 1984), LR 20:445 (April 1994), LR 30:1236 (June 2004).
AUTHORITY NOTE: Promulgated in accordance with R.S. 30:501 et seq.