La. Admin. Code tit. 17 § I-117

Current through Register Vol. 50, No. 11, November 20, 2024
Section I-117 - International Energy Conservation Code (Formerly LAC 55:VI.301.A.7)
A. International Energy Conservation Code (IECC) 2021 Edition and standards referenced in that code for regulation of construction in this state.

Amend

Section C301.2 Warm Humid counties

In Table C301.1, Warm Humid counties are identified by an asterisk but East Carroll and West Carroll shall be listed as Climate Zone 2A Hot Humid Climate

Amend

Section C402.1.3 Insulation component R-value-based method

Amend

Table C402.1.3 Opaque Thermal Envelope Insulation Component Minimum Requirements, R-Value

Methoda

Adopt

Exception

For those following a prescriptive path the requirement for slab insulation for unheated slabs Group R, Climate Zone 3, shall not be required and the table shall be listed as NR under that column.

Amend

Section C402.5.9 Vestibules

Amend

Exceptions

Amend

Item 1

Buildings in Climate Zones 0 through 1.

Amend

Section C403.4.1

The supply of heating and cooling energy to each zone shall be controlled by individual thermostatic controls capable of responding to temperature within the zone. Where humidification or dehumidification or both is provided, not fewer than one humidity control device shall be provided for each humidity control system. Where cooling is provided, the system shall be capable of limiting relative humidity levels to 60% relative humidity. Supplemental dehumidification equipment may be used to meet this requirement."

Amend

Section C403.5 Economizers

Amend

Item 2

Individual fan systems with cooling capacity greater than or equal to 65,000 Btu/h (15.8 kW) in buildings having other than a Group R occupancy,

Amend

Exception

Amend

Item 1

Individual fan systems not served by chilled water for buildings located in Climate Zones 0A, 0B, 1A,1B,2A and 3A

Amend

Item 6

Systems that include a heat recovery system in accordance with Section C403.10.5 and Section C403.10.6

Amend

Section C403.5.3.3 High-limit shutoff

Amend

Table C403.5.3.3 High-Limit Shutoff Control Setting For Air Economizersb

Remove Climate Zones 2A and 3A from the Fixed Dry Bulb Device Type

Amend

Section C403.7.4.2 Spaces other than nontransient dwelling units

Amend

Exception

Amend

Item 8

Where the total air exhausted from spaces served by an outdoor air system is less than 60% of the design outdoor air flow rate.

Amend

Section C403.7.6.1 Temperature setpoint controls

Amend

Item 2

When the guestroom is unrented and unoccupied, the controls shall automatically raise the cooling setpoint to not lower than 78°F (27°C) and lower the heating setpoint to not higher than 60°F (16°C). Unrented and unoccupied guestroom mode shall be initiated within 16 hours of the guestroom being continuously occupied or where a networked guestroom control system indicates that the guestroom is unrented and the guestroom is unoccupied for more than 20 minutes. A networked guestroom control system that is capable of returning the thermostat setpoints to default occupied setpoints 60 minutes prior to the time a guestroom is scheduled to be occupied is not precluded by this section. Cooling that is capable of limiting relative humidity with a setpoint not lower than 65-percent relative humidity during unoccupied periods is not precluded by this section.

Repeal

Section C405.5.3 Gas Lighting

Adopt

Residential Provisions

Amend

Section R102.1.1 Above code programs

The code official serving as the authority having jurisdiction for building codes, shall be permitted to deem a national or state energy-efficiency program to exceed the energy efficiency required by this code. Buildings approved in writing by such an energy-efficiency program shall be considered to be in compliance with this code. The requirements identified in Table N1105.2, as applicable, shall be met and the building thermal envelope is greater than or equal to levels of efficiency and solar heat gain coefficients (SHGC) in Tables 402.1.1 and 402.1.3 of the 2009 International Energy Conservation Code.

Adopt

Section R102.1.2 National Green Building Standard

Buildings complying with ICC 700-2020 National Green Building Standard and achieving an equivalent energy performance as demonstrated by a third-party certification organization shall be deemed to exceed the energy efficiency required by this code.

Adopt

Section R102.1.3 Energy Star Certification

Buildings receiving Energy Star Certification shall be deemed to exceed the energy efficiency required by this code.

Repeal

Section R103.2 Information on Construction Documents

Amend

Section R301.1 Climate Zones

Climate zones from Figure N1101.7 or Table N1101.7 shall be used for determining the applicable requirements in Sections N1101 through N1113. Locations not indicated in Table N1101.7 shall be assigned a climate zone in accordance with Section N1101.7.2. However, for energy purposes only, all of Louisiana shall be a climate zone 2A. East and West Carroll parishes shall be assigned a warm humid climate zone.

Adopt

Section R401.3 Louisiana Insulation Certificate requirement.

A State of Louisiana Insulation Certificate shall be permanently posted in a utility area.

Adopt

Section R401.3.1 Louisiana Insulation Certificate Template.

Click to view image

Click to view image

Amend

Section R402.2.1, Ceilings with attics

Adopt

Exception

Item (1.)

(1.) When the thermal covering at the roof line creates an unvented attic:

(a.) Proper sizing or modification of the HVAC system to the current code is required.

(b.) Any insulation between the sealed, conditioned attic space and the living space must be

removed.

Adopt

Item (2.)

(2.)(a) The space under appliances located in a sealed, conditioned attic may remain in place if sealed from the attic space, it is less than 10% of the total conditioned attic floor, and the appliances are approved for use in a sealed attic.

(b.) There shall be no outside attic ventilation and all openings must be blocked with rigid material and are sealed, in accordance with the ICC IRC Chapter 8 "Roof-Ceiling Construction

Amend

Section R402.2.3 Eave Baffle

For air-permeable insulation in vented attics, a baffle shall be installed adjacent to soffit and eave vents. Baffles shall maintain an opening equal to or greater than the size of the vent. The baffle shall extend over the top of the attic insulation. The baffle shall be permitted to be any solid material.

Amend

Section R402.2.7 Floors

Repeal

Subfloor insulation shall provide or be installed in permanent contact with a rigid air barrier material. If the building is cooled with air conditioning subfloors in any vented crawl space shall be insulated with an airtight, class II vapor retarder insulation system (perm < 1.0).

Adopt

Exception

Adopt

Item (1.)

(1.) Plastic Spray Foam cannot be applied to finish flooring where no subfloor exists.

Repeal

Section R402.4.1.1 Installation.

Amend

Section R402.4.1.2 Testing

The building or dwelling unit shall be tested for air leakage. The maximum air leakage rate for any building or dwelling unit under any compliance path shall not exceed 7.0 air changes per hour or 0.28 cubic feet per minute (CFM) per square foot [0.0079 m3/(s x m2)] of dwelling unit enclosure area. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380, ASTM E779 or ASTM E1827 and reported at a pressure of 0.2 inch w.g. (50 Pascals).Effective July 1, 2024, blower door testing shall be performed by individuals certified to perform blower door tests by a nationally recognized organization that trains and provides certification exams for the proper procedures to perform such tests. The responsible BCEO shall accept written blower door test reports from these certified individuals to verify the minimum requirements of Section N1102.4.1.2. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope have been sealed. Where multiple dwelling units or other occupiable conditioned spaces are contained within one building thermal envelope, each unit shall be considered an individual testing unit, and the building air leakage shall be the weighted average of all testing unit results, weighted by each testing unit's enclosure area. Units shall be tested separately with an unguarded blower door test as follows:

Adopt

Item (1.)

(1).Where buildings have fewer than eight testing units, each testing unit shall be tested.

Adopt

Item (2.)

(2) For buildings with eight or more testing units, the greater of seven units or 20 percent of the testing units in the building shall be tested, including a top floor unit, a ground floor unit and a unit with the largest testing unit enclosure area. For each tested unit that exceeds the maximum air leakage rate, an additional two units shall be tested, including a mixture of testing unit types and locations.

Amend

Exception

When testing individual dwelling units, an air leakage rate not exceeding 0.30 cubic feet per minute per square foot [0.008 m3/(s x m2)] of the dwelling unit enclosure area, tested in accordance with ANSI/RESNET/ICC 380, ASTM E779 or ASTM E1827 and reported at a pressure of 0.2 inch water gauge (50 Pa), shall be permitted in all climate zones for:

1. Attached single- and multiple-family building dwelling units.

2. Buildings or dwelling units that are 1,500 square feet (139.4 m2) or smaller.

Effective July 1, 2024, when a blower door test is performed, and the air infiltration rate of a dwelling unit is less than 3 air changes per hour when tested in accordance with Section N1102.4.1.2, the dwelling unit shall be provided with whole- house mechanical ventilation in accordance with Section M1507.3

Amend

Section R402.4.1.3 Leakage Rate

Where complying with Section N1101.13.1, the building or dwelling unit shall have an air leakage rate not exceeding 7.0 air changes per hour in Climate Zones 0, 1 and 2, and 7.0 air changes per hour in Climate Zones 3 through 8, when tested in accordance with Section N1102.4.1.2.

Amend

Section R402.4.4 Rooms containing fuel-burning appliances.

In Climate Zones 2 through 8, where open combustion air ducts provide combustion air to open combustion fuel-burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room that is isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table N1102.1.3, where the walls, floors and ceilings shall meet a minimum of the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section N1103. The combustion air duct shall be insulated where it passes through conditioned space to an R-value of not less than R-8.

Repeal

Section R402.4.6 Electrical and communication outlet boxes (air-sealed boxes)

Amend

Section R403.3.1 Ducts located outside conditioned space

Supply and return ducts located outside conditioned space shall be insulated to an R-value of not less than R-8.

Amend

Section 403.3.2 Ducts located in conditioned space.

Amend

Item 3.3

A minimum 10 insulation installed in the cavity width separating the duct from unconditioned space

Amend

Section R403.3.3 Ducts buried within ceiling insulation.

In Climate zone 2A Supply and Return ductwork shall not be buried in insulation

Repeal

Item 1

Repeal

Item 2

Repeal

Item 3

Amend

Section R403.3.5 Duct Testing

Duct leakage testing shall be performed by individuals certified to perform duct leakage tests by a nationally recognized organization that trains and provides certification exams for the proper procedures to perform such tests. The responsible BCEO shall accept written duct leakage test reports from these certified individuals to verify the minimum sealing requirements of Section N1103.3.4. Ducts shall be pressure tested in accordance with ANSI/RESNET/ICC 380 or ASTM E1554 to determine air leakage by one of the following methods:

Amend

Exceptions

Repeal

A duct air-leakage test shall not be required for ducts serving heating, cooling or ventilation systems that are not integrated with ducts serving heating or cooling systems.

Adopt

Item (1.)

(1.) A duct air-leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope.

Adopt

Item (2.)

(2.) HVAC contractors, who are not certified to perform duct leakage tests, may perform the test with the responsible BCEO visually verifying test procedures and results on site.

Amend

Section R403.3.6 Duct Leakage

Amend

Item (1.)

(1.) Rough-in test: The total leakage shall be less than or equal to 6.0 cubic feet per minute (113.3 L/min) per 100 square feet (9.29 m2) of conditioned floor area where the air handler is installed at the time of the test. Where the air handler is not installed at the time of the test, the total leakage shall be less than or equal to 4.0 cubic feet per minute (85 L/min) per 100 square feet (9.29 m2) of conditioned floor area.

Amend

Item (2.)

(2.) Post construction test: Total leakage shall be less than or equal to 8.0 cubic feet per minute (113.3 L/min) per 100 square feet (9.29 m2) of conditioned floor area or leakage to outside shall be less than or equal to 4 cfm per 100 sq feet of conditioned floor area.

Repeal

Item (3.)

Amend

Section R403.3.7 Building Cavities

Building framing cavities directly adjacent to and within shall not be used as ducts or plenums.

Amend

Section R403.6 Mechanical Ventilation

The buildings complying with Section N1102.4.1 providing mechanical ventilation shall comply with the requirements of Section M1505 or with other approved means of ventilation. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating.

Amend

Section R404.1 Lighting equipment

All permanently installed lighting fixtures, excluding kitchen appliance lighting fixtures, shall contain only high-efficacy lighting sources not less than 90 percent of the permanently installed lighting fixture.

Repeal

Section R404.1.1 Exterior Lighting

Repeal

Section R404.2 Interior lighting controls

Repeal

Section R404.3 Exterior Lighting controls

Amend

Section R406.2ERI Compliance

Repeal

Item (1.)

(1.) The requirements of the sections indicated within Table N1106.2

Amend

Section R406.3.2 On-site renewables are included

Where on-site renewable energy is included for compliance using the ERI analysis of Section N1106.4, the building thermal envelope shall be greater than or equal to the levels of efficiency and SHGC in Table R402.1.1 or R402.1.3 of the 2009 International Energy Conservation Code.

Amend

Section R406.4 Energy Rating Index

The Energy Rating Index (ERI) shall be determined in accordance with RESNET/ICC 301 Energy used to recharge or refuel a vehicle used for transportation on roads that are not on the building site shall not be included in the ERI reference design or the rated design.

Amend

Section R406.5 HERS-based compliance

Compliance based on an HERS analysis requires that the rated proposed design and confirmed built dwelling be shown to have an HERS less than or equal to the value of 58.

Adopt

Exceptions

Adopt

Item (1.)

(1.)HERS calculation method shall be an equivalent to the ERI analysis in calculating compliance

Adopt

Item (2.)

(2.)Other alternate means of home energy rating as approved by the building official

La. Admin. Code tit. 17, § I-117

Promulgated by the Department of Public Safety and Corrections, State Uniform Construction Code Council, LR 491136 (6/1/2023).
AUTHORITY NOTE: Promulgated in accordance with R.S. 40:1730.22(C) and (D) and 40:1730.26(1).

The amended version of this section by LR 49, is not yet available.