Subsurface soil absorption systems are the best available treatment technology and shall always be used where possible.
Table Ilia Maximum Soil Application Rates Based Upon Percolation Rates
Percolation Rate (minutes per inch) | Monthly Averages | |
Septic Tank Effluent(1) BOD530 mg/L - 220 mg/L TSS30mg/L- 150 mg/L (gals/sq ft/day)(2) | Pretreated Effluent BOD5 <= 30 mg/L TSS <= 30 mg/L (gals/sq ft/day) | |
0 to 5 | 1.2 | 1.6 |
Fine sands | 0.5 | 0.9 |
6 to 10 | 0.8 - 0.6 | 1.2 |
11 to 29 | 0.6 - 0.5 | 0.9 |
30 to 45 | 0.5 - 0.4 | 0.7 |
46 to 60 | 0.4 - 0.2 | 0.5 |
61 to 120 | 0.0 | 0.3 |
Greater than 120 | 0.0 | 0.0 |
NOTE: "BOD" means biochemical oxygen demand. "TSS" means total suspended solids.
Table Illb
Maximum Soil Loading Rates Based Upon Soil Evaluations in Gallons per Square Foot per Day (gal/ft2/day) for Septic Tank Effluent. Values in () are for secondary treated effluent.
Soil Texture | Single Grain | Massive | Structure Granular, Blocky, or Prismatic | Platy | |||
Weak | Moderate | Strong | Weak | Moderate to | |||
Strong | |||||||
Coarse sand and gravel | 1.2 (1.6) | X | 1.2 (1.6) | X | X | 1.2 (1.6) | X |
Medium sands | 0.7 (1.4) | X | 0.7 (1.4) | X | X | 0.7 (1.4) | X |
Fine sands | 0.5 (0.9) | X | 0.5 (0.9) | X | X | 0.5 (0.9) | X |
Very fine sands* | 0.3 (0.5) | X | 0.3 (0.5) | X | X | 0.3 (0.5) | X |
Sandy loam | X | 0.3 (0.5) | 0.45 (0.7) | 0.6 (1.1) | 0.65 (1.2) | 0.4 (0.6) | 0.3 (0.5) |
Loam | X | 0.4 (0.6) | 0.45 (0.7) | 0.5 (0.8) | 0.55 (0.8) | 0.4 (0.6) | 0.3 (0.5) |
Silty loam | X | NS | 0.4 (0.6) | 0.5 (0.8) | 0.5 (0.8) | 0.3 (0.5) | 0.2 (0.3) |
Clay loam | X | NS | 0.2 (0.3) | 0.45 (0.7) | 0.45 (0.7) | 0.1 (0.2) | 0.1 (0.2) |
Silty clay loam | X | NS | 0.2 (0.3) | 0.45 (0.7) | 0.45 (0.7) | NS | NS |
NOTE: "X" means not found in nature. "NS" means not suitable for soil absorption.
* Flow rates are difficult to determine for some very fine sands; experience may provide better information and flow rates.
Table IIIc
Minimum Length of Absorption Trenches in Feet
2 bedroom 300 gal. | 3 bedroom 450 gal. | 4 bedroom 600 gal. | 5 bedroom 750 gal. | 6 bedroom 900 gal. | ||||||
Width of trench in feet | 2' | 3' | 2' | 3' | 2' | 3' | 2' | 3' | 2' | 3' |
Soil loading rate gal/ft2 | ||||||||||
0.1 | Not suitable for soil absorption trenches | |||||||||
0.2 | 750 | 500 | 1125* | 750 | 1500* | 1000* | 1875* | 1250* | 2250* | 1500* |
0.3 | 500 | 333 | 750 | 500 | 1000* | 666 | 1250* | 833* | 1500* | 1000* |
0.4 | 375 | 250 | 562 | 375 | 750 | 500 | 938* | 625 | 1125* | 750 |
0.5 | 300 | 200 | 450 | 300 | 600 | 400 | 750 | 500 | 900* | 600 |
0.6 | 250 | 167 | 375 | 250 | 500 | 333 | 625 | 417 | 750 | 500 |
0.7 | 214 | 143 | 321 | 214 | 428 | 286 | 536 | 357 | 643 | 429 |
0.8 | 188 | 125 | 281 | 188 | 375 | 250 | 469 | 312 | 562 | 375 |
0.9 | 167 | 111 | 250 | 167 | 333 | 222 | 417 | 278 | 500 | 333 |
1.0 | 150 | 100 | 225 | 150 | 300 | 200 | 375 | 250 | 450 | 300 |
1.1 | 136 | 91 | 205 | 136 | 273 | 182 | 341 | 227 | 409 | 273 |
1.2 | 125 | 84 | 188 | 125 | 250 | 167 | 313 | 208 | 375 | 250 |
* Requires pressure distribution (pump)
Table IIId
Alternative Option for Use of Absorption Bed*
Percolation Rate min./inch | Absorption Area/Bedroom sq. ft. | Loading Rate/Day gal./sq. ft. |
1 - 5 | 300 | .5 |
6-15 | 400 | .375 |
16 -30 | 600 | .25 |
*Absorption beds may only be used when site space restrictions require and shall not be used when the soil percolation rate exceeds 30 min./inch.
Iowa Admin. Code r. 567-69.9