Section 675 IAC 20-3-10 - Disinfectant equipment and chemical feedersAuthority: IC 22-13-2-2
Affected: IC 22-12; IC 22-13; IC 22-15; IC 36-7
Sec. 10.
Disinfectant equipment and chemical feeders shall be as follows:
(1) Capable of automatically providing a continuous residual chemical effect in accordance with 410 IAC, the rules of the Indiana state department of health.(3) Installed downstream from the pump.(4) Wired so they will not operate unless the filter pump is operating. An exception is erosion-type chlorinators may feed their solution to the suction side of the pump.