Section 675 IAC 16-1.4-8 - Chapter 7; sanitary drainageAuthority: IC 22-13-2
Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7-2-9
Sec. 8.
Chapter 7 is amended as follows:
(a) Amend Table 704.1 as follows: delete "0.083.3 mm/m" and insert "83.3 mm/m".(b) Amend Section 705.8.2 as follows: delete "purple" and "not purple in color and," without substitution.(c) Amend Table 702.2 as follows: under "Copper or copper alloy tubing", delete without substitution "M or DWV".(d) Amend Section 705.14.2 as follows: delete "purple" and "not purple in color and" without substitution.(e) Amend Section 706.3 as follows: after "combination fittings", delete "side inlets or".(f) Delete the fourth sentence in Section 708.3.5 without substitution.(g) Amend Table 710.1(2) as follows: In the second column, delete "2,900" and insert "3,900".(h) Add Section 710.3 to read as follows: 710.3 Minimum underground drainage size. The minimum pipe size installed underground in a sanitary drainage system within a building shall be two (2) inch nominal (50.8 mm) pipe size.Fire Prevention and Building Safety Commission; 675 IAC 16-1.4-8; filed Sep 25, 2012, 2:42 p.m.: 20121024-IR-675110448FRA, eff 90 days after filing with the PublisherReadopted filed 7/3/2018, 2:22 p.m.: 20180801-IR-675180204RFAReadopted filed 6/10/2024, 8:09 a.m.: 20240710-IR-675230794RFA