675 Ind. Admin. Code 14-4.4-9

Current through December 4, 2024
Section 675 IAC 14-4.4-9 - Section R302.11; fireblocking

Authority: IC 22-13-2-2; IC 22-13-2-2.5; IC 22-13-2-13

Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7

Sec. 9.

Change the text of ITEM 4 of SECTION R302.11 to read as follows:

4. At openings around vents, pipes, ducts, cables, and wires at ceilings and floor level, with an approved material to resist the free passage of flame and products of combustion. The material filling this annular space shall not be required to meet the ASTM E136 requirements but shall have an ignition point at or above that of white pine wood, 350° F (177° C), and where surrounding electrical cables shall meet the requirements of E3705.4.4.

675 IAC 14-4.4-9

Fire Prevention and Building Safety Commission; 675 IAC 14-4.4-9; field 11/26/2019, 11:43 a.m.: 20191225-IR-675190330FRA