Add SECTION R314.8 to read as follows:
SECTION R314.8 VISIBLE NOTIFICATION APPLIANCES.
In addition to the smoke alarms required in this section, listed visible notification appliances, when installed, shall comply with the following:
SECTION R314.8.1 CANDELA RATING - SLEEPING ROOM.
A visible notification appliance, when installed in a room designed for sleeping, shall have a minimum rating of 177 candela, except that when the visible notification appliance is wall mounted or suspended more than 24 inches (610 mm) below the ceiling, a minimum rating of 110 candela is permitted.
SECTION R314.8.2 CANDELA RATING - NONSLEEPING ROOM.
A visible notification appliance, when installed in an area other than a room designed for sleeping, shall have a minimum rating of 15 candela.
675 IAC 14-4.4-26