675 Ind. Admin. Code 14-4.4-209

Current through December 4, 2024
Section 675 IAC 14-4.4-209 - Section E3704.4; lighting and general use receptacle load

Authority: IC 22-13-2-2; IC 22-13-2-2.5; IC 22-13-2-13

Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7

Sec. 209.

Add a sentence to the end of the text of SECTION E3704.4 to read as follows:

A further demand factor of 70 percent shall be permitted for that portion of the unbalanced load in excess of 200 amps.

(220.12, Table 220.12, and 220.14(J))

675 IAC 14-4.4-209

Fire Prevention and Building Safety Commission; 675 IAC 14-4.4-209; filed 11/26/2019, 11:43 a.m.: 20191225-IR-675190330FRA