675 Ind. Admin. Code 14-4.4-197

Current through December 4, 2024
Section 675 IAC 14-4.4-197 - Section E3601.6.2; service disconnect location

Authority: IC 22-13-2-2; IC 22-13-2-2.5; IC 22-13-2-13

Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7

Sec. 197.

Add a sentence to the end of SECTION E3601.6.2 to read as follows:

Conductors shall be considered outside of a building or structure under any of the following conditions:

1. where installed under not less than 2 inches (51 mm) of concrete beneath a building or other structure;
2. where installed within a building or other structure in a raceway that is encased in concrete or brick not less than 2 inches thick; or
3. where installed in conduit and under not less than 18 inches (457 mm) of earth beneath a building or other structure.

675 IAC 14-4.4-197

Fire Prevention and Building Safety Commission; 675 IAC 14-4.4-197; filed 11/26/2019, 11:43 a.m.: 20191225-IR-675190330FRA