675 Ind. Admin. Code 14-4.4-168

Current through December 4, 2024
Section 675 IAC 14-4.4-168 - Section P2912.15; tests

Authority: IC 22-13-2-2; IC 22-13-2-2.5; IC 22-13-2-13

Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7

Sec. 168.

Change SECTION P2912.15 as follows:

(1) Change the title and text of SECTION P2912.15 to read as follows:

SECTION P2912.15 TESTS. Tests shall be performed in accordance with Sections P2912.15.1 through P2912.15.8.

(2) Change the title and text of SECTION P2912.15.1 to read as follows:

SECTION P2912.15.1 ROOF GUTTER TEST.

Roof gutters shall be tested to verify that the installation and slope is in accordance with Section P2912.5.1. Gutters shall be tested by pouring not less than 1 gallon of water (3.8 L) into the end of the gutter opposite the collection point. The gutter being tested shall not leak and shall not retain standing water.

675 IAC 14-4.4-168

Fire Prevention and Building Safety Commission; 675 IAC 14-4.4-168; filed 11/26/2019, 11:43 a.m.: 20191225-IR-675190330FRA