(3) The maximum width of the aggregate bed shall meet the following requirements: (A) The maximum aggregate bed width (ft.)(ABW) = 0.83 ft2/gpd Click here to view Image
DDF (gpd) | n |
[LESS THAN OR EQUL TO]1500 | 3 |
1501-3000 | 4 |
3001-4000 | 5 |
where: 0.83 is a conversion factor (ft2/gpd)
SLR is soil loading rate, and
where: DDF is design daily flow, and
n is determined by the DDF in this chart
This number may be rounded down to the nearest whole number.
(B) For on-site sewage systems with a DDF of seven hundred fifty (750) gallons per day or less, the width of the aggregate bed shall be at least four (4) feet and not greater than ten (10) feet. The aggregate bed width shall not exceed the maximum bed width calculated in clause (A).(C) For on-site sewage systems with a DDF of greater than seven hundred fifty (750) gallons per day, the following apply: (i) If the soil loading rate is fifty-hundredths (0.50) gallons per day per square foot (gpd/ft2) or less, the width of the aggregate bed shall be not greater than fifteen (15) feet, and shall not exceed the maximum bed width calculated in clause (A).(ii) If the soil loading rate is greater than fifty-hundredths (0.50) gallons per day per square foot (gpd/ft2), the width of the aggregate bed shall be not greater than twenty (20) feet, and shall not exceed the maximum bed width calculated in clause (A).