Authority: IC 13-14-8-1; IC 13-14-8-2; IC 13-19-3
Affected: IC 13-11-2; IC 13-14; IC 13-19; IC 13-20; IC 13-22; IC 13-23; IC 13-30
Sec. 2.
Used oil burned for energy recovery, and any fuel produced from used oil by processing, blending, or other treatment, is subject to regulation under this article unless it is shown not to exceed any of the allowable levels of the constituents and properties in the specification shown in Table 1. Once used oil that is to be burned for energy recovery has been shown not to exceed any specification and the person making that showing complies with 329 IAC 13-9-3, 329 IAC 13-9-4, and 329 IAC 13-9-5(b), the used oil is no longer subject to this article.
Table 1-Used Oil not Exceeding any Specification Level is not Subject to this Article when Burned for Energy Recovery1
Constituent or Property | Allowable Level |
Arsenic | 5 ppm maximum |
Cadmium | 2 ppm maximum |
Chromium | 10 ppm maximum |
Lead | 100 ppm maximum |
Flash point | 100° F minimum |
Total halogens | 4,000 ppm maximum2 |
Note: Applicable standards for the burning of used oil containing PCBs are imposed by 40 CFR 761.20(e).
329 IAC 13-3-2