210 Ind. Admin. Code 8-4-17

Current through December 4, 2024
Section 210 IAC 8-4-17 - Heating and cooling systems

Authority: IC 11-8-2-5; IC 31-31-8-2

Affected: IC 31-31-8

Sec. 17.

(a) Written policy, procedure, and practice provide that heating, ventilation, and cooling systems ensure healthful living and working conditions for juveniles and staff with temperatures appropriate to the:
(1) summer; and
(2) winter; comfort zones.
(b) Circulation is at least fifteen (15) cubic feet of outside or recirculated filtered air per minute, per occupant, for the following:
(1) Sleeping rooms.
(2) Common areas.
(3) Staff stations.
(4) Dining areas.
(c) Measurements are documented by a qualified source at least every three (3) years.

210 IAC 8-4-17

Department of Correction; 210 IAC 8-4-17; filed 9/16/2022, 3:13 p.m.: 20221012-IR-210220072FRA