A minimum of one centrally located nurse station shall be provided for the birth unit. The number of birth rooms shall be provided as determined by the program narrative, but shall not exceed 10 beds.
The birth rooms shall be clustered in groups, shall be located out of the path of unrelated traffic, and shall be under direct supervision of the nurse station. The birth room will serve as labor, delivery and recovery room. The birth rooms should also be located in an area adjacent to the respite nursery (if provided).
Birth rooms shall be adequate and appropriate to provide for equipment, staff, supplies and emergency procedures required for the physical and emotional care of a maternal client, her support person and the newborn during labor, birth and the recovery period.
Birth rooms shall have an outside window. The window is not required to be operable.
Each birth room shall be equipped with a hand-washing sink with hands-free operation acceptable for scrubbing. Hand-washing sinks shall be large enough and with an integral drain board and deep sink for infant bathing when not in use for hand washing.
All finishes shall be kept clean and shall be of the type that is appropriate for the cleaning methods and solutions required to maintain a clean and safe environment.
Lighting shall be provided to accommodate the needs of the client and delivery team, during labor, during a delivery, and postpartum, and to permit the examination and treatment of the infant in the infant resuscitation area.
A respite nursery may be provided to allow for the rest of the mother when requested. The nursery shall be located and accessible from the nurse station and shall meet the criteria established for newborn nurseries contained in Section 2.1.3.6.6 of the AIA Guidelines for Design and Construction of Health Care Facilities.
The size and location of each support area shall depend on the numbers and types of modalities served. The following support areas shall be readily available in each birth center when required by the program narrative. Identifiable spaces are required for each of the indicated functions.
Charting facilities shall have a linear surface space to ensure that staff and physicians can chart and have simultaneous access to information and communication systems.
Appropriate provisions shall be made for the distribution of medications.
Each nurse station shall have equipment to provide ice for treatments and nourishment.
Such rooms shall be separate from and have no direct connection with soiled workrooms or soiled holding rooms. If the clean workroom is used for preparing client care items, it shall contain a work counter, a hand-washing station, and storage facilities for clean and sterile supplies.
Such rooms shall be separate from and have no direct connection with clean work rooms or clean supply rooms and shall contain the following:
A housekeeping room shall be provided at the ratio of one housekeeping closet per 10 birth rooms. The room shall:
Toilet rooms for staff and visitors shall be conveniently located in the birth unit. Client toilet rooms cannot satisfy this requirement.
Securable lockers, closets, and cabinet compartments for the personal articles of staff shall be located in or near the nurse station.
Each birth center shall provide for storing and processing of clean and soiled linen for appropriate client care. Processing may be done within the center, in a separate building on or off site, or in a commercial or shared laundry.
Sufficient space shall be included in all mechanical and electrical equipment rooms for proper maintenance of equipment. Provisions shall also be made for removal and replacement of equipment. The following shall be provided:
Rooms shall be provided for boilers, mechanical, and electrical equipment.
Storage for solvents and flammable liquids shall comply with NFPA 30.
Yard equipment and supply storage areas shall be provided. These shall be located so that equipment may be moved directly to the exterior without interference with other work.
An entrance at grade level, sheltered from inclement weather, and accessible to handicapped persons (in accordance with the Illinois Accessibility Code) shall be provided.
Ill. Admin. Code tit. 77, § 265.2750