Ill. Admin. Code tit. 77, pt. 250, subpt. W, tbl. B

Current through Register Vol. 48, No. 50, December 13, 2024
Table B - Sound Transmission Limitations in General Hospitals

SOUND TRANSMISSION LIMITATIONS IN GENERAL HOSPITALS

Airborne Sound Transmissions Class (STC)a

Impact Insulation Class (11C)b

Patitions

Floors

Floors

Patients' Room to Patients' Room

45

45

45

Public space to Patients' Roomc

50

50

50d

Service areas to Patients' Roome

55

55

55d

a Sound transmission class (STC) shall be determined by tests in accordance with methods set forth in ASTM Standard E 90 and ASTM Standard E 413.

b Impact insulation class (11C) shall be determined in accordance with criteria set forth in HUD FT/TS-24, "A Guide to Airborne, Impace and Structure Borne Noise-Control in Multi-Family Dwellings."

c Public space includes Lobbies, Dining Rooms, Recreation Rooms, Treatment Rooms, and similar spaces.

d Impact noise limitation applicable only when Corridor, Public Space, Service Area, or Play or Recreation Area is over patients' room.

e Service areas include Kitchens, Elevator, Elevator Machine Rooms, Laundries, Garages, Maintenance Rooms, Boiler and Mechanical Equipment Rooms, and similar spaces of high noise. Mechanical equipment located on the same floor or above Patients' Rooms, Offices, Nurses Stations, and similar occupied spaces shall be effectively isolated from the floor.

Ill. Admin. Code tit. 77, pt. 250, subpt. W, tbl. B