Current through Register Vol. 48, No. 49, December 6, 2024
Section 604.705 - Chlorination Equipmenta) Procedure for Submitting Plans and Specifications - Design documents for chlorination must be prepared and submitted in accordance with 35 Ill. Adm. Code 602.b) Chlorination equipment must: 1) be large enough to satisfy the immediate chlorine demand and give a measurable residual of at least 2.0 mg/L of total chlorine under all operating conditions after contact;2) be capable of feeding chlorine to the water being treated at a dosage rate of at least 5.0 mg/L, except when the water has a high chlorine demand. Factors in determining chlorine demand are: D) presence in the water of substances having chlorine demand such as hydrogen sulfide, iron, manganese and nitrogenous compounds including ammonia; andE) supplemental treatment such as aeration that reduces chlorine demand;3) be provided in duplicate when operating conditions do not allow repair of the chlorinator during off-pumping periods;4) be provided in duplicate, installed and operational, at community water supplies treating surface water, groundwater under the direct influence of surface water, and groundwater with a history of total coliform positive results; and5) include spare parts for emergency repairs consisting of at least the commonly expendable parts such as glassware, fittings, hose clamps, and gaskets.Ill. Admin. Code tit. 35, § 604.705
Adopted in R18-17 at 43 Ill. Reg. 8064, effective 7/26/2019.