Where:
Nact = Image
Nall = Image
Nact | = | Total sum of the actual NOx mass emissions from units included in the averaging plan for each fuel used (lbs per ozone season and calendar year). |
Nall | = | Total sum of the allowable NOx mass emissions from units included in the averaging plan for each fuel used (lbs per ozone season and calendar year). |
EMall(i) | = | Total mass of allowable NOx emissions in lbs for a unit as determined in subsection (g)(2) or (h)(2) of this Section. |
EMact(i) | = | Total mass of actual NOx emissions in lbs for a unit as determined in subsection (g)(1) or (h)(1) of this Section. |
i | = | Subscript denoting an individual unit and fuel used. |
n | = | Number of different units in the averaging plan. |
Where:
EMact(i) | = | Total mass of actual NOx emissions in lbs for a unit, except as provided for in subsections (g)(3) and (g)(5) of this Section. |
EMall(i) | = | Total mass of allowable NOx emissions in lbs for a unit, except as provided for in subsection (g)(3) of this Section. |
Eact | = | Actual NOx emission rate (lbs/mmBtu) calculated according to the above equation. |
Eall | = | Allowable NOx emission rate (lbs/mmBtu) calculated according to the above equation, as applicable. |
H | = | Heat input (mmBtu/ozone season or mmBtu/year) calculated from fuel flow meter and the heating value of the fuel used. |
Cd(act) | = | Actual concentration of NOx in lb/dscf (ppmv x 1.194 x10-7) on a dry basis for the fuel used. Actual concentration is determined on each of the most recent test runs or monitoring passes performed pursuant to Section 217.394, whichever is higher. |
Cd(all) | = | Allowable concentration of NOx in lb/dscf (allowable emission limit in ppmv specified in Section 217.388(a)(1), except as provided for in subsection (g)(4), (g)(5), (g)(6), or (g)(7) of this Section, if applicable, multiplied by 1.194 x 10-7) on a dry basis for the fuel used. |
Fd | = | The ratio of the gas volume of the products of combustion to the heat content of the fuel (dscf/mmBtu) as given in the table of F Factors included in 40 CFR 60, appendix A, Method 19 or as determined using 40 CFR 60, appendix A, Method 19. |
%O2d | = | Concentration of oxygen in effluent gas stream measured on a dry basis during each of the applicable tests or monitoring runs used for determining emissions, as represented by a whole number percent, e.g., for 18.7%O2d, 18.7 would be used. |
i | = | Subscript denoting an individual unit and the fuel used. |
j | = | Subscript denoting each test run or monitoring pass for an affected unit for a given fuel. |
m | = | The number of test runs or monitoring passes for an affected unit using a given fuel. |
Where:
EMall elec(i) | = | Mass of allowable NOx emissions from the electric-powered replacement unit in pounds per ozone season or calendar year. |
bhp | = | Nameplate capacity of the electric-powered replacement unit in brake horsepower. |
OP | = | Operating hours during the ozone season or calendar year. |
F | = | Conversion factor of 0.0077 mmBtu/bhp-hr. |
Eall rep(i) | = | Allowable NOX emission rate (lbs/mmBtu) of the replaced unit. |
i | = | Subscript denoting an individual electric unit and the fuel used. |
Where:
EMall(i) | = | Total mass of allowable NOx emissions in lbs for a unit. |
flowji | = | Stack flow (dscf/hr) for a given stack. |
Cdj | = | Allowable concentration of NOx (ppmv) specified in Section 217.388(a)(1) for a given stack (1.194 x 10-7 converts to lb/dscf). |
j | = | subscript denoting each hour operation of a given unit. |
m | = | Total number of hours of operation of a unit. |
i | = | Subscript denoting an individual unit and the fuel used. |
Ill. Admin. Code tit. 35, § 217.390
Amended at 33 Ill. Reg. 11999, effective August 6, 2009