Haw. Code R. § 6-77-34

Current through November, 2024
Section 6-77-34 - Temperature derating factor (T) for steel pipe

The temperature derating factor to be used in the design formula in section 6-77-29 is determined as follows:

Gas temperature in degrees Fahrenheit | Temperature derating factor (T)
250 or less.............................................| 1.000
300................................................| 0.967
350................................................| 0.933
400................................................| 0.900
450................................................| 0.867

For intermediate gas temperatures, the derating factor is determined by interpolation.

Haw. Code R. § 6-77-34

[Eff ] (Auth: HRS § 269-6) (Imp: 49 C.F.R. §192.115, OCT 1, 1990)