Section 12-45.2-73 - Fire department communication system

Section 13.7.2.27.2.2 is amended to read as follows: "A two-way, fire department communication system approved by the AHJ shall be provided for fire department use. A jack or plug receptacle shall be located at the following locations:

1. The emergency command center/central location approved by the AHJ.
2. The designated fire service elevator(s)
3. Each elevator lobby on each floor of the building.
4. Emergency and standby power rooms.
5. The stairwell side of each exit into each required stairway.

The height of the jack or plug receptacle shall be not more than 5 feet and not less than 3 feet above floor level. Portable hand sets in compliance with the following provisions shall be provided by the building owner or management for fire department use:

1. Not less than 10 approved-type portable hand sets shall be stored and maintained in the central control station.
2. Length of cord for portable hand sets shall be provided as recommended and approved by the AHJ.
3. Hand sets approved by the AHJ shall be maintained in an operative condition at all times and shall be replaced or repaired when found to be defective."