Section 20.16.1.1 is amended to read as follows: "An emergency command center room for fire department operations shall be provided in high-rise buildings. The location and accessibility of the emergency command center room shall be approved by the AHJ. The room shall be accessible from the exterior of the building. The central control station room shall be separated from the remainder of the building by not less than a one-hour fire-resistive occupancy separation. The room shall be a minimum of 96 (9 m2) square feet with a minimum dimension of 8 feet (2438 mm). It shall contain the following as a minimum:
Control panels in the emergency command center shall be permanently identified as to function.
Alarm, supervisory and trouble signals as required by Items 3 and 7 above shall be annunciated in compliance with the fire code in the emergency command center by means of an audible and visual indicator."
Haw. Code R. § 12-45.2-106