Mechanical and ventilation systems, including but not limited to furnaces, gas- or oil-fired room heaters, and water heaters in barber, cosmetology, and personal grooming facilities shall comply with the most recent versions of the District of Columbia Construction Codes, as specified in § 102.1(g)(2), and other applicable District laws and regulations.
All barber and cosmetology facilities shall have sufficient tempered make-up air and exhaust ventilation to keep them free of excessive heat, steam, condensation, vapors, obnoxious odors, smoke, and fumes.
All personal grooming facilities shall allow for circulation of air sufficient to eliminate odors in accordance with § 102.1(g)(2).
All rooms in a barber, cosmetology, and personal grooming facilities shall be provided with at least eight (8) air changes per hour. Recirculation of air is not permitted.
Nail salons, including nail work stations within a cosmetology, or personal grooming facility that provide manicure and/or pedicure services shall be equipped with an independent exhaust or mechanical ventilation system at the source capture system to remove fumes and dust from nail stations directly to the exterior of the building and shall not be recirculated into any space. Make-up air is required and shall be considered for the entire mechanical exhaust ventilation system design, as specified in § 309.6 and Table A in § 309.7.
An independent source capture system exhaust and mechanical ventilation system shall be located at each nail station with an interlocking exhaust system and light switch to ensure the exhaust system is fully operational when nail station activities are occurring.
The minimum flow rate of outdoor air that the ventilation system must be capable of supplying during its operation shall be based on the rate per person, and the actual number of occupants' present, as specified in Table A:
TABLE A
OCCUPANCY CLASSIFICATION | OCCUPANT DENSITY #/1000 FT2a | PEOPLE OUTDOOR AIRFLOW RATE IN BREATHING ZONE,RpCFM/PERSON | AREA OUTDOOR AIRFLOW RATE IN BREATHING ZONE,RaCFM/FT2a | EXHAUST AIRFLOW RATE CFM/FT2 |
Barber | 25 | 7.5 | 0.06 | 0.5 |
Beauty salonsb | 25 | 20 | 0.12 | 0.6 |
Nail salons b, h | 25 | 20 | 0.12 | 0.6 |
For SI: 1 cubic foot per minute = 0.0004719 m3/s, 1 ton = 908 kg, 1 cubic foot per minute per square foot = 0.00508 m3/(s ·m2),°C =[(°F)-32]/1.8, 1 square foot = 0.0929 m2.
D.C. Mun. Regs. tit. 25, r. 25-E309