Rule 25-C502 - EQUIPMENT ROOMS - VENTILATION AND ACCESS*
502.1

Equipment rooms shall have either forced draft or cross ventilation.

502.2

All below grade equipment rooms shall have a stairway access with forced draft ventilation or a fully louvered door and louvered vent on at least one other side.

502.3

Where stairway access is not necessary to carry heavy items into the below grade room or vault, a "ship's ladder" may be used if approved by the Department.

502.4

The opening to an equipment room shall be a minimum of three feet by six feet (3 ft. x 6 ft.) and shall provide easy access to the equipment.

502.5

A hose bibb with vacuum breaker shall be located in the equipment room.

502.6

A carbon monoxide detector with local alarming, listed and labeled in accordance with UL Standard 2075, shall be installed in all equipment rooms and rooms adjacent to spaces containing fuel-burning equipment or vents carrying the products of combustion.