D.C. Mun. Regs. tit. 15, r. 15-2362
Current through Register Vol. 72, No. 2, January 10, 2025
The meter shall not leak when subjected to pressure and shall be checked for leaks in the following manner:
Tinned steel case meters shall be subjected to an internal pressure of at least two pounds (2 lbs.) per square inch gauge (psig) when testing for leaks.
Iron or aluminum case meters shall be tested at a pressure at least fifty percent (50%) above operating pressure. The meters may be sample tested in accordance with the plan described in § 2360.11. If one (1) or more meters in the sample is found to leak, additional testing shall be done as described in § 2360.11.
D.C. Mun. Regs. tit. 15, r. 15-2362