Strike Section 804.3 of the International Existing Building Code in its entirety and insert new Section 804.3 in the Existing Building Code in its place to read as follows:
Standpipes. Where the work area includes exits or corridors located more than 50 feet (15 240 mm) above or below the lowest level of fire department access, a standpipe system shall be provided. Standpipes shall have an approved fire department connection with hose connections at each floor level above or below the lowest level of fire department access. Standpipe systems shall be installed in accordance with the Building Code
Exceptions:
D.C. Mun. Regs. tit. 12, r. 12-J804