TABLE 9.6.1 LIGHTING POWER DENSITY ALLOWANCES USING THE SPACE-BY-SPACE METHOD AND MINIMUM CONTROL REQUIREMENTS USING EITHER METHOD
Strike TABLE 9.6.1 Lighting Power Density Allowances Using the Space-by-Space Method and Minimum Control Requirements Using Either Method, in ASHRAE 90.1 and insert new Table 9.6.1 in its place in the Energy Conservation Code-Commercial Provisions to read as follows:
TABLE 9.6.1 Lighting Power Density Allowances Using the Space-by-Space Method and Minimum Control Requirements Using Either Method
Informative Note: This table is divided into two sections; this first section covers space types that can be commonly found in multiple building types. The second part of this table covers space types that are typically found in a single building type. | The control functions below shall be implemented in accordance with the descriptions found in the referenced paragraphs within Section 9.4.1.1. For each space type: (1) All REQs shall be implemented. (2) At least one ADD1 (when present) shall be implemented. (3) At least one ADD2 (when present) shall be implemented | ||||||||||
Local Control (See Section 9.4.1.1[a]) | Restricted to Manual ON (See Section 9.4.1.1[b]) | Restricted to Partial Automatic ON (See Section 9.4.1.1[c]) | Bilevel Lighting Control (See Section 9.4.1.1[d]) | Automatic Daylight Responsive Controls for Sidelighting (See Section 9.4.1.1[e]6) | Automatic Daylight Responsive Controls for Toplighting (See Section 9.4.1.1[f]6 | Automatic Partial OFF (See Section 9.4.1.1[g] [Full Off complies]) | Automatic Full OFF (See Section 9.4.1.1[h]) | Scheduled Shutoff (See Section 9.4.1.1[i]) | |||
Common Space Types1 | LPD, W/ft2 | RCR Threshold | a | b | c | d | e | f | g | h | i |
Atrium | |||||||||||
... that is <20 ft in height ... that is >20 ft and <40 ft in height ... that is >40 ft in height 0 | 0.03/ft total height 0.03/ft total height . 0 + 0.02/ft total | NA NA NA | REQ REQ REQ | ADD1 ADD1 ADD1 | ADD1 ADD1 ADD1 | - REQ REQ | REQ REQ REQ | REQ REQ REQ | - - - | ADD2 ADD2 ADD2 | ADD2 ADD2 ADD2 61 |
Audience Seating Area | |||||||||||
... in an auditorium | 0.63 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in a convention center | 0.82 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
. in a gymnasium | 0.65 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in a motion picture theater | 1.14 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in a penitentiary | 0.28 | 4 | REQ | ADD1 | ADD1 | - | REQ | REQ | - | ADD2 | ADD2 |
... in a performing arts theater | 2.43 | 8 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in a religious building | 1.53 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in a sports arena | 0.43 | 4 | REQ | ADD1 | ADD1 | - | REQ | REQ | - | ADD2 | ADD2 |
... all other audience seating areas | 0.43 | 4 | REQ | ADD1 | ADD1 | - | REQ | REQ | - | ADD2 | ADD2 |
Banking Activity Area | 1.01 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Breakroom | |||||||||||
(See Lounge/Breakroom) | |||||||||||
Classroom/Lecture Hall/Training Room | |||||||||||
... in a penitentiary | 1.34 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | REQ | - |
... all other classrooms/lecture halls/ training rooms | 1.24 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | REQ | - |
Conference/Meeting/Multipurpose Room | 1.10 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | REQ | - |
Confinement Cells | 0.81 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Copy/Print Room | 0.72 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | REQ | - |
Corridor2 | |||||||||||
... in a facility for the visually impaired | 0.92 | width <8 ft | REQ | - | - | - | REQ | REQ | REQ | ADD2 | ADD2 |
(and not used primarily by the staff)3 | 0.99 | width <8 ft | REQ | - | - | - | REQ | REQ | ADD2 | ADD2 | ADD2 |
0.41 | width <8 ft | REQ | - | - | - | REQ | REQ | - | ADD2 | ADD2 | |
0.56 | width <8 ft | REQ | - | - | - | REQ | REQ | REQ | ADD2 | ADD2 | |
... all other corridors Courtroom | 1.46 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Computer Room | 1.71 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Dining Area | |||||||||||
... in a penitentiary | 0.96 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in a facility for the visually impaired (and not used primarily by staff)3 | 2.65 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in bar/lo unge or leisure dining | 1.07 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in cafete ria or fast food dining | 0.65 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in family dining | 0.75 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... all other dining areas | 0.58 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Electrical/Mechanical Room7 | 0.42 | 6 | REQ | - | - | - | REQ | REQ | - | - | - |
Emergency Vehicle Garage | 0.56 | 4 | REQ | ADD1 | ADD1 | - | REQ | REQ | - | ADD2 | ADD2 |
Food Preparation Area | 1.21 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Guest Room | 0.91 | 6 | Se | e Section 9.4.1.3b. | |||||||
Laboratory | |||||||||||
... in or as a classroom | 1.43 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | REQ | ADD2 | ADD2 |
... all other laboratories | 1.71 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Laundry/Washing Area | 0.57 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Loading Dock, Interior | 0.47 | 6 | REQ | ADD1 | ADD1 | - | REQ | REQ | - | ADD2 | ADD2 |
Lobby | |||||||||||
... in a facility for the visually impaired (and not used primarily by the staff)3 | 1.80 | 4 | REQ | - | - | - | REQ | REQ | REQ | ADD2 | ADD2 |
... for an elevator | 0.54 | 6 | REQ | - | - | - | REQ | REQ | - | ADD2 | ADD2 |
... in a hotel | 1.06 | 4 | REQ | - | - | - | REQ | REQ | - | ADD2 | ADD2 |
... in a motion picture theater | 0.56 | 4 | REQ | - | - | - | REQ | REQ | - | ADD2 | ADD2 |
... in a performing arts theater | 2.00 | 6 | REQ | - | - | - | REQ | REQ | REQ | ADD2 | ADD2 |
... all other lobbies | 0.85 | 4 | REQ | - | - | - | REQ | REQ | REQ | ADD2 | ADD2 |
Locker Room Lounge/Breakroom | 0.75 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | REQ | - |
... in a healthcare facility | 0.78 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | REQ | - |
... all other lounges/breakrooms | 0.62 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | REQ | - |
Office ... enclosed and <250 ft 2 | 1.05 | 8 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | REQ | - |
... enclosed and >250 ft2 | 1.05 | 8 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... open plan | 0.93 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Parking Area, Interior | 0.19 | 4 | See | Section 9.4.1.2 | ... | ||||||
Pharmacy Area | 1.68 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Restroom | |||||||||||
... in a facility for the visually impaired (and not used primarily by the staff)3 | 1.21 | 8 | REQ | - | - | - | REQ | REQ | - | REQ | - |
... all other restrooms | 0.98 | 8 | REQ | - | - | - | REQ | REQ | - | REQ | - |
Sales Area4 | 1.36 | 6 | REQ | ADD1 | ADD1 | REQ | - | REQ | - | ADD2 | ADD2 |
Seating Area, General | 0.54 | 4 | REQ | ADD1 | ADD1 | - | REQ | REQ | - | ADD2 | ADD2 |
Stairway | The space | containing the stair | way shall determ | ine the LPD an | d control requir | ements for the s | tairway. | ||||
Stairwell | 0.69 | 10 | REQ | - | - | REQ | REQ | REQ | REQ | ADD2 | ADD2 |
Storage Room | |||||||||||
... <50 ft2 | 1.24 | 6 | REQ | - | - | - | - | - | - | ADD2 | ADD2 |
... >50 ft 2 and < 1000 ft 2 | 0.63 | 6 | REQ | ADD1 | ADD1 | - | REQ | REQ | - | REQ | - |
... all other storage rooms | 0.63 | 6 | REQ | ADD1 | ADD1 | - | REQ | REQ | REQ | ADD2 | ADD2 |
Vehicular Maintenance Area | 0.67 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Workshop | 1.59 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Facility for the Visually Impaired3 ... in a chapel (used primarily by residents) | 2.21 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in a recreation room/common living room (and not used primarily by staff) | 2.41 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Automotive (See "Vehicular Maintenance Area") Convention Center- Exhibit Space | 1.23 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Dormitory-Living Quarters Fire | 0.38 | 8 | REQ | - | - | - | - | - | - | - | - |
Station-Sleeping Quarters Facility | 0.22 | 6 | REQ | - | - | - | - | - | - | - | - |
for the Visually Impaired 3 | |||||||||||
Gymnasium/Fitness Center | |||||||||||
... in an exercise area | 0.61 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in a playing area | 1.20 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Healthcare Facility | |||||||||||
... in an exam/treatment room | 1.41 | 8 | REQ | - | - | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in an imaging room | 1.51 | 6 | REQ | - | - | REQ | - | - | - | ADD2 | ADD2 |
....in a medical supply room | 0.66 | 6 | ( | See "Storage R | oom" under "Co | mmon Space T | ypes" for control | requirements) | |||
... in a nursery | 0.74 | 6 | REQ | - | - | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in a nurse's station | 0.63 | 6 | REQ | - | - | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in an operating room | 2.48 | 6 | REQ | - | - | REQ | - | - | - | ADD2 | ADD2 |
... in a patient room | 0.55 | 6 | REQ | - | - | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in a physical therapy room | 0.77 | 6 | REQ | - | - | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in a recovery room Library | 1.15 | 6 | REQ | - | - | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in a reading area | 1.06 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in the stacks | 1.62 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | REQ | ADD2 | ADD2 |
Manufacturing Facility | |||||||||||
... in a detailed manufacturing area | 1.29 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in an equipment room | 0.74 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in an extra high bay area (>50 ft floor-to-ceiling height) | 1.05 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in a high bay area (25-50 ft floor-to-ceiling height) | 1.04 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in a low bay area (<25 ft floor-to-ceiling height) | 1.01 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Museum ... in a general exhibition area | 1.05 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in a restoration room | 1.02 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Performing Arts Theater- Dressing Room | 0.61 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | REQ | - |
Post Office-Sorting Area Religious Buildings | 0.94 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | REQ | ADD2 | ADD2 |
... in a fellowship hall | 0.64 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... in a worship/pulpit/choir area | 1.53 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Retail Facilities | |||||||||||
... in a dressing/fitting room | 0.71 | 8 | REQ | ADD1 | ADD1 | REQ | REQ | - | REQ | - | |
... in a mall concourse | 1.10 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Sports Arena-Playing Area | |||||||||||
... for a Class I facility | 3.68 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... for a Class II facility | 2.40 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... for a Class III facility | 1.80 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
... for a Class IV facility | 1.20 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Transportation Facility | |||||||||||
... in a baggage/carousel area | 0.47 | 4 | REQ | ADD1 | ADD1 | - | REQ | REQ | - | ADD2 | ADD2 |
... in an airport concourse | 0.32 | 4 | REQ | ADD1 | ADD1 | - | REQ | REQ | - | ADD2 | ADD2 |
... at a terminal ticket counter | 0.68 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | - | ADD2 | ADD2 |
Warehouse-Storage Area | |||||||||||
...for medium to bulky, palletized items | 0.49 | 4 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | REQ | ADD2 | ADD2 |
... for smaller, hand-carried items5 | 0.95 | 6 | REQ | ADD1 | ADD1 | REQ | REQ | REQ | REQ | ADD2 | ADD2 |
TABLE 9.6.3 Control Factors Used in Calculating Additional Interior Lighting Power Allowance
Space Type | |||||
Additional Control Method (in Addition to Mandatory Requirements) | Open Office | Private Office | Conference Room, Meeting Room, Classroom (Lecture/ Training) | Retail Sales Area | Lobby, Atrium, Dining Area, Corridors/ Stairways, Gym/ Pool, Mall Concourse, Parking Garage |
Manual, continuous dimming control or programmable multilevel dimming control | 0.05 | 0.05 | 0.10 | 0.10 | 0 |
Programmable multilevel dimming control using programmable time scheduling | 0.05 | 0.05 | 0.10 | 0.10 | 0.10 |
Occupancy sensors controlling the downlight component of workstation specific luminaires with continuous dimming to off capabilities | 0.25a | 0 | 0 | 0 | 0 |
Occupancy sensors controlling the downlight component of | |||||
workstation specific luminaires with continuous dimming to off operation, in combination with personal continuous dimming control of downlight illumination by workstation occupant | 0.30a,b | 0 | 0 | 0 | 0 |
Automatic continuous daylight dimming in secondary sidelighted areas | 0.10c | 0.10c | 0.10c | 0.10c | 0.10c |
Strike Section 9.6.2 of ASHRAE 90.1 in its entirety and insert a new Section 9.6.2 in its place in the Energy Conservation Code-Commercial Provisions to read as follows:
Additional Interior Lighting Power. When using the Space-by-Space Method, an increase in the interior lighting power allowance is allowed for specific lighting functions. Additional power shall be allowed only if the specified lighting is installed and automatically controlled, separately from the general lighting, to be turned off during nonbusiness hours. This additional power shall be used only for the specified luminaires and shall not be used for any other purpose unless otherwise indicated.
An increase in the interior lighting power allowance is permitted in the following cases:
+ (For Retail Area 2, 10% base power allowance for the sales area per Table 9.5.1 or Table 9.6.1)
+ (For Retail Area 3, 30% base power allowance for the sales area per Table 9.5.1 or Table 9.6.1)
+ (For Retail Area 4, 50% base power allowance for the sales area per Table 9.5.1 or Table 9.6.1),
Retail Area 1 = the floor area for all products not listed in Retail Areas 2, 3, or 4
Retail Area 2 = the floor area used for the sale of vehicles, sporting goods, and small electronics
Retail Area 3 = the floor area used for the sale of furniture, clothing, cosmetics, and artwork
Retail Area 4 = the floor area used for the sale of jewelry, crystal, and china
Exception: Other merchandise categories may be included in Retail Areas 2 through 4 above, provided that justification documenting the need for additional lighting power based on visual inspection, contrast, or other critical display is approved by the authority having jurisdiction.
Strike Section 9.6.3 of ASHRAE 90.1 in its entirety and insert a new Section 9.6.3 in its place to read as follows:
Prescriptive Controls.Building projects shall comply with the prescriptive control requirements of 9.5.2, 9.5.3, 9.5.4, and 9.5.5.