D.C. Mun. Regs. tit. 12, 12-I8.5

Current through Register Vol. 71, No. 49, December 6, 2024
Section 12-I8.5 - PRESCRIPTIVE PATH
8.5.1

Automatic Control of Equipment in Hotel/Motel Guest Rooms. In hotels and motels with more than 50 guest rooms, automatic controls for switched outlets and televisions serving each guest room shall be configured according to the following requirements.

8.5.1.1

Switched Outlet Control. Within 30 minutes of all occupants leaving the guest room, power for lighting and switched outlets shall be automatically turned off.

8.5.1.2

Television Control. Within 30 minutes of all occupants leaving the guest room, televisions shall be automatically turned off or placed in sleep or standby mode.

D.C. Mun. Regs. tit. 12, 12-I8.5

Final Rulemaking published at 67 DCR 5679 (5/29/2020)