Insert a new Section 5.4.1.1 in the Energy Conservation Code-Commercial Provisions to read as follows:
Accounting for Thermal Conduction Components. Where a component of the building envelope assembly reduces the overall U-value of the rest of the assembly, that component shall be thermally represented and integrated into the area-weighted U-value as described by the following default methodology. This default methodology shall be used in all energy compliance pathways including: Prescriptive U-value compliance, Section 5.6 Trade-off, and Appendix G energy model. Prescriptive R-value compliance with Table 5.5 and the energy model baseline shall assume Default Cladding Attachment Coefficients = 1 from Table 5.4.1.1(1) and no Linear Anomalies as described in Table 5.4.1.1(2). Tables 5.4.1.1(1) and 5.4.1.1(2) shall be used in conjunction with Equation 5.4.1.1 and associated default calculation methodology to account for common thermal conduction situations not currently described in Appendix A. In lieu of the equation and methodology the project team may demonstrate to the authority having jurisdiction two dimensional heat flow modeling, three dimensional heat flow modeling, linear transmission calculations per ASHRAE D RP-1365, or hot box-testing results showing the resultant area-weighted U-value as acceptable to the authority having jurisdiction. If using this alternate methodology, all thermal bridges described by ASHRAE D RP-1365 shall be represented.
Exceptions:
Where
Ubw = "Overall U-Factor for Entire Base Wall Assembly" (such as from ASHRAE
90.1 , Normative Appendix A, Table A3.3, A3.4 - Insulation in stud cavity, plus gypsum, thermal boundary layers)
Re = Nominal Exterior insulation R-value (From Project Design)
Cac = Cladding Attachment Coefficient (from Table 5.4.1.1(1))
Wac = Wall Anomaly Coefficient (from Table 5.4.1.1(2))
Default Methodologies:
Option A - Specification Approach:
Option B - Simplified Approach:
Option C - Detailed Approach:
See following Tables:
Table 5.4.1.1(1) | - Default Cladding Attachment Coefficient | |
Attachment type through Rigid Insulation | Material and/or Orientation | Cladding Attachment Coefficient, Cac |
Girts | Metal Vertical girt (Detail 1*) | 53% |
Horizontal Metal girt (Detail 2*) | 62% | |
Horizontal Non-Metal girt | 100% | |
Clips | Metal Clips | 75% |
Stainless Steel Clips | 85% | |
Thermal Stop Clips | 90% | |
Fiberglass Clip | 100% | |
Brick Ties | Steel Brick Ties | 78% |
Stainless Steel Brick Ties | 90% | |
Thermal Break Brick Ties | 100% | |
Long Screws | Galvanized Long Screws | 80% |
Stainless Long Screws | 100% |
*Detail Associated with ASHRAE D RP-1365
Table 5.4.1.1(2) - Default Linear Anomaly Coefficient for Vertical Assembly | ||||
Construction Type | Wall Linear Anomaly | Insulation Placement | ASHRAE D RP -1365 Detail # | Wall Anomaly Coefficient, Wac |
All Wall Facades | Concrete Balcony or Concrete Floor | Uninsulated at top and bottom, exterior and in stud cavity insulation | 5 | 36% |
Concrete Balcony or Concrete Floor | Insulated at top of slab, exterior and in stud cavity insulation | 5 | 39% | |
Concrete Balcony or Concrete Floor | insulated at top and bottom of slab, exterior and in stud cavity insulation | 5a | 42% | |
All Facades with Structural Steel | Steel Support for Floor | Interior Insulated Wall | 16 | 64% |
Steel Support for Floor | Exterior & Interior Insulated | 17 | 80% | |
Metal or Masonry Parapet | Exterior Rigid and Interior Framed | 10 | 72% | |
Brick Facade | Concrete Slab with Standard Metal Shelf Angle or Metal Flashing | Exterior Rigid and Interior Framed | 14 | 54% |
Concrete Slab with Reduced-Contact Metal Shelf Angle | Exterior Rigid and Interior Framed | 15 | 65% | |
Metal or Masonry Parapet | Both sides insulated with rigid, with Roof insulation | 9 | 100% | |
Metal or Masonry Parapet | Interior wall metal framed insulation with roof insulation | 20 | 65% | |
Spandrel Panels | Slab Intersection | No Stud Insulation and Back Pan Insulation | 22 | 34% |
Slab Intersection | Stud Insulation and Back Pan Insulation | 23 | 44% | |
Metal or Masonry Parapet | Stud Insulation and Back Pan Insulation | 25 | 41% | |
Precast Walls | Slab Intersection Metal or Masonry Parapet | Interior Metal Framed Insulation Exterior Metal Framed Insulation | 29 30 | 73% 76% |
Slab Intersection | Sandwich Panel, at slab intersection | 32 | 63% | |
Metal or Masonry Parapet | Sandwich Panel, at roof intersection | 33 | 65% | |
Concrete Block With Exterior Rigid Insulation | Metal Shelf Angle | Exterior Rigid and Metal Shelf Angle | 35 | 62% |
Reduced Contact Shelf Angle | Exterior Rigid and Reduced Contact Shelf Angle | 36 | 70% | |
Metal or Masonry Parapet | Brick Ties at Parapet and Roof | 37 | 69% | |
No Linear Anomalies as Described Above | All | All | - | 100% |
Strike Exception 2 to Section 5.4.3.2 of ASHRAE 90.1 in its entirety without substitution:
Strike Section 5.4.3.4 of ASHRAE 90.1 in its entirety and insert a new Section 5.4.3.4 in its place in the Energy Conservation Code-Commercial Provisions to read as follows:
Vestibules.Building entrances that separate conditioned space from the exterior shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices. Vestibules shall be designed so that in passing through the vestibule it is not necessary for the interior and exterior doors to open at the same time. Interior and exterior doors shall have a minimum distance between them of not less than 7 ft when in the closed position. The floor area of each vestibule shall not exceed the greater of 50 ft2 or 2% of the gross conditioned floor area for that level of the building. The exterior envelope of conditioned vestibules shall comply with the requirements for a conditioned space. The interior and exterior envelope of unconditioned vestibules shall comply with the requirements for a semiheated space.
Exceptions:
[No change to Section 5.4.3.4.1 ]
Insert a new Section 5.4.4 in ASHRAE 90.1 to read as follows:
On-Site Renewable Energy Systems.Building project design shall show allocated space and pathways for future installation of on-site renewable energy systems and associated infrastructure to cover no less than 25% of horizontal projection of the gross roof area.
Exceptions:
D.C. Mun. Regs. tit. 12, 12-I5.4