D.C. Mun. Regs. tit. 12, 12-I5.4

Current through Register Vol. 71, No. 49, December 6, 2024
Section 12-I5.4 - MANDATORY PROVISIONS

Insert a new Section 5.4.1.1 in the Energy Conservation Code-Commercial Provisions to read as follows:

5.4.1.1

Accounting for Thermal Conduction Components. Where a component of the building envelope assembly reduces the overall U-value of the rest of the assembly, that component shall be thermally represented and integrated into the area-weighted U-value as described by the following default methodology. This default methodology shall be used in all energy compliance pathways including: Prescriptive U-value compliance, Section 5.6 Trade-off, and Appendix G energy model. Prescriptive R-value compliance with Table 5.5 and the energy model baseline shall assume Default Cladding Attachment Coefficients = 1 from Table 5.4.1.1(1) and no Linear Anomalies as described in Table 5.4.1.1(2). Tables 5.4.1.1(1) and 5.4.1.1(2) shall be used in conjunction with Equation 5.4.1.1 and associated default calculation methodology to account for common thermal conduction situations not currently described in Appendix A. In lieu of the equation and methodology the project team may demonstrate to the authority having jurisdiction two dimensional heat flow modeling, three dimensional heat flow modeling, linear transmission calculations per ASHRAE D RP-1365, or hot box-testing results showing the resultant area-weighted U-value as acceptable to the authority having jurisdiction. If using this alternate methodology, all thermal bridges described by ASHRAE D RP-1365 shall be represented.

Exceptions:

1. Electrical wiring used for transmission of energy.
2. Plumbing penetrations complying with prescriptive insulation requirements of Section 7.
3. Mechanical penetrations complying with prescriptive insulation requirements of Section 6.
4. Non-metal flashing for moisture management.

Where

Ubw = "Overall U-Factor for Entire Base Wall Assembly" (such as from ASHRAE

90.1 , Normative Appendix A, Table A3.3, A3.4 - Insulation in stud cavity, plus gypsum, thermal boundary layers)

Re = Nominal Exterior insulation R-value (From Project Design)

Cac = Cladding Attachment Coefficient (from Table 5.4.1.1(1))

Wac = Wall Anomaly Coefficient (from Table 5.4.1.1(2))

Default Methodologies:

Option A - Specification Approach:

1) If complying with the Prescriptive R-value requirements per Table 5.5-4 the building project must have:
a. No Linear Anomalies for Vertical Assemblies as described in Table 5.4.1.1
b. For projects using exterior insulation "Materials and/or Orientations" identified in Table 5.4.1.1(1) with Cladding Attachment Coefficients (Cac) of 1 shall be explicitly specified in the drawings and/or specifications.

Option B - Simplified Approach:

1) Find the lowest Default Linear Anomaly for Vertical Assembly applicable to the proposed design. Use this value to include in Equation 5.4.1.1
2) Determine the Default Cladding Attachment Coefficient for the proposed design
3) Use equation 5.4.1.1 to determine U-value(OverallincludingThermalBridges) for vertical walls
4) Use the calculated U-value(OverallincludingThermalBridges) for compliance with prescriptive U-value compliance per Table 5.5-4, Trade off method section 5.6 (via COMCheck), or the proposed energy model via Appendix G.
5) Calculations and assumptions shall be presented to the authority having jurisdiction

Option C - Detailed Approach:

1) Define a new rectangular vertical wall area associated with one Default Linear Anomaly per story, or part of a story (includes stories below grade)
2) If there is more than one Default Linear Anomaly per vertical, rectangular wall section (for example such as a wall with both a concrete balcony and a parapet), select the lowest Default Linear Anomaly Coefficient for Vertical Assembly and use that for Equation 5.4.1.1
3) Determine the Default Cladding Attachment Coefficient for the proposed design wall section.
4) Use equation 5.4.1.1 to determine U-value(OverallincludingThermalBridges)
5) Use the calculated U-value(OverallincludingThermalBridges) for compliance with prescriptive U-value compliance per Table 5.5-4, Trade off method section 5.6 (via COMCheck), or the proposed energy model via Appendix G.
6) Each unique vertical wall assembly shall be evaluated and/or included for the compliance Options C step 5
7) Calculations and assumptions shall be presented to the authority having jurisdiction

See following Tables:

Table 5.4.1.1(1)

- Default Cladding Attachment Coefficient

Attachment type through Rigid Insulation

Material and/or Orientation

Cladding Attachment Coefficient, Cac

Girts

Metal Vertical girt (Detail 1*)

53%

Horizontal Metal girt (Detail 2*)

62%

Horizontal Non-Metal girt

100%

Clips

Metal Clips

75%

Stainless Steel Clips

85%

Thermal Stop Clips

90%

Fiberglass Clip

100%

Brick Ties

Steel Brick Ties

78%

Stainless Steel Brick Ties

90%

Thermal Break Brick Ties

100%

Long Screws

Galvanized Long Screws

80%

Stainless Long Screws

100%

*Detail Associated with ASHRAE D RP-1365

Table 5.4.1.1(2) - Default Linear Anomaly Coefficient for Vertical Assembly

Construction Type

Wall Linear Anomaly

Insulation Placement

ASHRAE D

RP -1365

Detail #

Wall Anomaly Coefficient, Wac

All Wall Facades

Concrete Balcony or Concrete Floor

Uninsulated at top and bottom, exterior and in stud cavity insulation

5

36%

Concrete Balcony or Concrete Floor

Insulated at top of slab, exterior and in stud cavity insulation

5

39%

Concrete Balcony or Concrete Floor

insulated at top and bottom of slab, exterior and in stud cavity insulation

5a

42%

All Facades with Structural Steel

Steel Support for Floor

Interior Insulated Wall

16

64%

Steel Support for Floor

Exterior & Interior Insulated

17

80%

Metal or Masonry Parapet

Exterior Rigid and Interior Framed

10

72%

Brick Facade

Concrete Slab with

Standard Metal Shelf

Angle or Metal Flashing

Exterior Rigid and Interior Framed

14

54%

Concrete Slab with

Reduced-Contact Metal

Shelf Angle

Exterior Rigid and Interior Framed

15

65%

Metal or Masonry Parapet

Both sides insulated with rigid, with Roof insulation

9

100%

Metal or Masonry Parapet

Interior wall metal framed insulation with roof insulation

20

65%

Spandrel Panels

Slab Intersection

No Stud Insulation and Back Pan Insulation

22

34%

Slab Intersection

Stud Insulation and Back Pan Insulation

23

44%

Metal or Masonry Parapet

Stud Insulation and Back Pan Insulation

25

41%

Precast Walls

Slab Intersection Metal or Masonry Parapet

Interior Metal Framed

Insulation

Exterior Metal Framed

Insulation

29 30

73% 76%

Slab Intersection

Sandwich Panel, at slab intersection

32

63%

Metal or Masonry Parapet

Sandwich Panel, at roof intersection

33

65%

Concrete Block

With Exterior Rigid Insulation

Metal Shelf Angle

Exterior Rigid and Metal Shelf Angle

35

62%

Reduced Contact Shelf Angle

Exterior Rigid and Reduced Contact Shelf Angle

36

70%

Metal or Masonry Parapet

Brick Ties at Parapet and Roof

37

69%

No Linear

Anomalies

as Described

Above

All

All

-

100%

Strike Exception 2 to Section 5.4.3.2 of ASHRAE 90.1 in its entirety without substitution:

Strike Section 5.4.3.4 of ASHRAE 90.1 in its entirety and insert a new Section 5.4.3.4 in its place in the Energy Conservation Code-Commercial Provisions to read as follows:

5.4.3.4

Vestibules.Building entrances that separate conditioned space from the exterior shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices. Vestibules shall be designed so that in passing through the vestibule it is not necessary for the interior and exterior doors to open at the same time. Interior and exterior doors shall have a minimum distance between them of not less than 7 ft when in the closed position. The floor area of each vestibule shall not exceed the greater of 50 ft2 or 2% of the gross conditioned floor area for that level of the building. The exterior envelope of conditioned vestibules shall comply with the requirements for a conditioned space. The interior and exterior envelope of unconditioned vestibules shall comply with the requirements for a semiheated space.

Exceptions:

1. Revolving doors;
2. Doors not intended to be used as a building entrance, including service entrance doors;
3. Doors opening directly from a dwelling unit;
4. Doors that open directly from a space that is less than 3,000 ft2 in area;
5. Semiheated spaces;
6. Enclosed elevator lobbies for building entrances directly from parking garages.

[No change to Section 5.4.3.4.1 ]

Insert a new Section 5.4.4 in ASHRAE 90.1 to read as follows:

5.4.4

On-Site Renewable Energy Systems.Building project design shall show allocated space and pathways for future installation of on-site renewable energy systems and associated infrastructure to cover no less than 25% of horizontal projection of the gross roof area.

Exceptions:

1.Building projects that have an annual daily average incident solar radiation available to a flat plate collector oriented due south at an angle from horizontal equal to the latitude of the collector location less than 1.2 kBtu/ft2·day (4.0 kWh/m2·day), accounting for existing buildings, permanent infrastructure that is not part of the building project, topography, or trees.
2.Building projects that comply with Section 13.1.

D.C. Mun. Regs. tit. 12, 12-I5.4

Final Rulemaking published at 67 DCR 5679 (5/29/2020)