On-Site Renewable Energy Systems. Building projects shall comply with either the Standard Renewables Approach in Section 13.1.1.1 or the Alternate Renewables Approach in Section 13.1.1.2 where any of the following conditions are met:
Exceptions: Buildings that demonstrate compliance with both of the following conditions are not required to contain on-site renewable energy systems:
Standard Renewables Approach: Baseline On-Site Renewable Energy Systems.Building projects shall contain on-site renewable energy systems that provide the annual energy production equivalent of not less than 6.0 kBtu/ ft2 (20 kWh/m2 ) multiplied by the gross roof area in ft2 (m2) for single-story buildings, and not less than 10.0 kBtu/ft (32 kWh/m) multiplied by the gross roof area in ft (m) for all other buildings. The annual energy production shall be the combined sum of all on-site renewable energy systems.
Alternate Renewables Approach: Reduced On-Site Renewable Energy Systems and Higher-Efficiency Equipment.Building projects complying with this approach shall comply with the applicable equipment efficiency requirements in Normative Appendix B of ASHRAE 189.1 (Prescriptive Equipment Efficiency Tables for the Alternate Reduced Renewables and Increased Equipment Efficiency Approach in Section 7.4.1.1.2), the water-heating efficiency requirements in Section 7.4.4.1 of ASHRAE 189.1, equipment efficiency requirements in Section 10.6 of ASHRAE 189.1, ® and the applicable ENERGY STAR requirements in Section 10.11.2 of 189.1, and shall contain on-site renewable energy systems that provide the annual energy production equivalent of not less than 4.0 kBtu/ft (13 kWh/m) multiplied by the gross roof area in ft (m) for single-story buildings, and not less than 7.0 kBtu/ft (22 kWh/m) multiplied by the gross roof area in ft (m ) for all other buildings. The annual energy production shall be the combined sum of all on-site renewable energy systems. For equipment listed in Section 10.11.2 of ASHRAE 189.1 that is also contained in Normative Appendix B of ASHRAE 189.1, the installed equipment shall comply by meeting or exceeding both requirements.
Exception: If building project includes less than 75% of build-out of net-occupiable floor area, then the project team cannot use Alternate Renewables Approach in 13.1.1.2, and shall use the Standard Renewables Approach in 13.1.1.1.
D.C. Mun. Regs. tit. 12, 12-I13.1