Strike Section 3103.1 of the International Fire Code in its entirety and insert a new Section 3103.1 in the Fire Code in its place to read as follows:
General.Tents and membrane structures erected for a period of 180 days or less shall comply with this section. Other temporary structures erected for a period of 180 days or less shall comply with Section 3103 of the Building Code.
Exception: Membrane structures erected on a building, balcony, deck or other structure for any period of time shall comply with Sections 3102.1 through 3102.8 of the Building Code.
Strike Section 3103.2 of the International Fire Code in its entirety and insert a new Section
3103.2 in the Fire Code in its place to read as follows:
Approval required.Tents and membrane structures that cover an area of 150 square feet (13.9 m2)or greater including connecting areas or spaces with a common means of egress or entrance that are used or intended to be used for the gathering together of 10 or more persons, shall not be erected, operated or maintained for any purpose without first obtaining a permit from the building code official and, where required, an operational permit from the fire code official.
Exceptions:
Strike Section 3103.4 of the International Fire Code in its entirety and insert new Section 3103.4 in the Fire Code in its place to read as follows:
Permits.Permits shall be required in accordance with Section 105 of the Building Code. An operational permit issued by the fire code official, pursuant to Section 106, shall also be required where applicable.
D.C. Mun. Regs. tit. 12, r. 12-H3103