Strike Section 210.64 in Article 210 of the National Electrical Code in its entirety and insert a new Section 210.64 into the Electrical Code in its place to read as follows:
Electrical Service Areas. At least one 125-volt, single-phase, 20-ampere-rated GFCI receptacle outlet shall be installed within 7.5m (25 ft) of the electrical service equipment
Exception: The receptacle outlet shall not be required to be installed in one- and two-family dwellings.
Strike the title of Section 408, Article 408 of the National Electrical Code and insert a new title for Section 408 into the Electrical Code in its place to read as follows:
D.C. Mun. Regs. tit. 12, r. 12-C210.64