Insert new Section 903.3.1.2.3 in the Building Code to read as follows:
Attics. Attic protection shall be provided as follows:
Strike Section 903.4.2 of the International Building Code in its entirety and insert new Section 903.4.2 in the Building Code in its place to read as follows:
Alarms. An approved audible device, located on the exterior of the building in an approved location, shall be connected to each automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in t he system. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system.
Exceptions: An alarm device shall not be required on the exterior of the building when the sprinkler system is monitored by an approved central station, remote supervising station or proprietary supervising station in accordance with NFPA 72.
Insert a new Section 903.4.4 into the Building Code to read as follows:
Where a sprinkler system is looped such that more than one control valve must closed to stop flow from that zone, a sign shall be placed at each control valve indicating the locations of the other control valves for that zone.
D.C. Mun. Regs. tit. 12, r. 12-A903