D.C. Mun. Regs. tit. 12, r. 12-A2702

Current through Register Vol. 71, No. 49, December 6, 2024
Rule 12-A2702 - EMERGENCY AND STANDBY POWER SYSTEMS
2702.1.7

Group I-2 Occupancies. In Group I-2 occupancies located in flood hazard areas established in Section 1612.3, where new essential electrical systems are installed, and where new essential electrical system generators are installed, the systems and generators shall be located and installed in accordance with ASCE 24. Where connections for hookup of temporary generators are provided, the connections shall be located at or above the elevation required in ASCE 24.

D.C. Mun. Regs. tit. 12, r. 12-A2702

Final Rulemaking published at 68 DCR 7439 (7/30/2021)