Current through Register Vol. 28, No. 7, January 1, 2025
Section 701-4-5.0 - Required Building Plan Information5.1 Information required to accompany building plans shall include but not be limited to: 5.1.1 Name and address of building;5.1.2 Owner of the building;5.1.3 Name and address of applicant submitting plans;5.1.4 Design Professional's name and address;5.1.5 Detailed construction information;5.1.6 Narrative description of building occupancy and operations;5.1.7 Full height cross section plan of building including all vertical openings, shafts, enclosures, etc.;5.1.8 Note whether building is to be sprinklered and, if so, what areas;5.1.9 Detailed HVAC information;5.1.10 Specific information on all means of egress components including clear widths, fire resistance rating, direction swing of doors and locking mechanisms on exit doors;5.1.11 Location of all "hazardous" or "high hazard areas" as defined in the Life Safety Code, NFPA 101;5.1.12 Floor plan of seats, tables, displays, decorations, etc. in all places of assembly which do not have permanent seating or displays;5.1.13 Electrical plan including location of exit signs and emergency lighting when required;5.1.14 Detailed information pertaining to any detection or alarm systems to be installed including but not limited to the make, type and location of all associated equipment; and5.1.15 Narrative description of proposed method for sealing penetrations of fire rated assemblies.1 Del. Admin. Code § 701-4-5.0