The adopted National Fire Protection Association standard NFPA 101® is amended to meet the needs of the State of Connecticut as follows:
Note:
A section or subsection in the Connecticut Amendments preceded by "Amd" indicates the substitution of this provision in the adopted referenced standard, National Fire Protection Association Standard 101, Life Safety Code®, 2003 edition.
A section or subsection in the Connecticut Amendments preceded by "Del" indicates the deletion of this provision in the adopted referenced standard.
A section or subsection in the Connecticut Amendments preceded by "Add" indicates the addition of this provision in the adopted referenced standard.
A section or subsection in the Connecticut Amendments followed by an asterisk "*" indicates that explanatory material on the section or subsection can be found in Appendix A of the adopted referenced standard.
Chapter 1 *
Administration
(Del) 1.1.1 Delete section.
(Amd) 1.1.3 Egress Facilities. The code establishes minimum criteria for egress facilities so as to allow prompt escape of occupants from buildings or, where desirable, into safe areas within buildings.
(Del) 1.3.1* Delete section.
(Del) 1.6 Delete section.
Chapter 2
Referenced Publications
(Del) 2.2 NFPA Publications. Delete section.
(Del) 2.3.4 ASME Publications. Delete section.
Chapter 3
Definitions
(Amd) 3.3.27* Building. Any structure used or intended for supporting or sheltering any use or occupancy. For application of this code, each portion of a building which is completely separated from other portions by fire walls which have been designed and constructed in accordance with the State Building Code and have been approved by the building official shall be considered separate buildings.
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Add) 3.3.152.12.1 Bed and Breakfast or Bed and Breakfast Establishment. A building:
(Amd) 3.3.191* Self-Preservation (Day-Care Occupancy). The ability of a client to evacuate a day-care occupancy without direct intervention by a staff member. Clients under the age of 3 years shall be considered incapable of self-preservation.
Chapter 4
General
(Del) 4.5 Fundamental Requirements. Delete section.
(Del) 4.6.1.2 Delete section.
(Del) 4.6.1.3 Delete section.
(Del) 4.6.3* Delete section.
(Del) 4.6.4* Delete section.
(Amd) 4.6.8* Existing life safety features that do not meet the requirements for new buildings, but that exceed the requirements for existing buildings, shall not be further diminished.
(Del) 4.6.11.2* Delete section.
(Del) 4.7 Delete section.
(Del) 4.8 Delete section.
Chapter 5
Performance-Based Options
(Del) Delete Chapter.
Chapter 6
Classification of Occupancy and Hazard of Contents
(Add) 6.1.8.1.6 Definition - Bed and Breakfast or Bed and Breakfast Establishment. An existing building:
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
Chapter 7
Means of Egress
(Amd) 7.1.3.2.1 Where this code requires an exit to be separated from other parts of the building, the separating construction shall meet the requirements of 8.2 and the following:
(Amd) 7.1.5.1 Means of egress shall be designed and maintained to provide headroom in accordance with other sections of this code, and such headroom shall be not less than 2285 mm (90 in.), with projections from the ceiling not less than 2030 mm (80 in.) nominal above the finished floor, unless otherwise specified in 7.1.5.1.1 through 7.1.5.1.4.
(Add) 7.1.5.1.3 In existing buildings, the projections from the ceiling are permitted but not more than 1830 mm (72 in.) nominal above the finished floor where the projection is provided with padding and illumination by both normal and emergency sources.
(Add) 7.1.5.1.4 Door closers and stops shall not reduce the headroom to less than 1981 mm (78 in).
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Amd) 7.2.1.2.3.2 For swinging doors, projections of not more than 100 mm (4 in.) into the doorway width shall not be considered reductions in width, provided that such projections are located not less than 865 mm (34 in.) above the floor.
(Amd) 7.2.1.3.3 Thresholds at doorways shall not exceed 13 mm (1/2 in.) in height or 19.1 mm (3/4 in.) in height for sliding doors serving dwelling units.
(Amd) 7.2.1.4.3 A door shall swing in the direction of egress travel under any of the following conditions:
(Amd) 7.2.1.6.2 Access-Controlled Egress Doors. Where permitted in Chapter 11 through Chapter 42, entrance doors to buildings and tenant spaces in the means of egress shall be permitted to be equipped with an approved entrance and egress access control system, provided that the following criteria are met:
(Amd) 7.2.2.1.2 The requirements of 7.2.2.1.1 shall not apply to aisle steps as provided in Chapter 13.
(Add) 7.2.2.2.1.1 Existing stairs shall be permitted to remain in use if the minimum width clear of all obstructions, except projections not more than 114 mm (41/2 in.) at or below handrail height on each side is 710 mm (28 in.) and the total occupant load of all floors served by the stair is fewer than 30 persons.
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Add) 7.2.2.2.4.4 Existing stairs containing winders may be continued in use provided all of the following are met:
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Del) 7.2.2.5.2* Delete section.
(Amd) 7.2.2.6.3.1 Outside stairs shall be separated from the interior of the building by construction with the fire resistance rating required for enclosed stairs with fixed or self-closing opening protectives, except as follows:
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Del) 7.2.12.3.2 Delete section.
(Amd) Table 7.3.1.2 Occupant Load Factor
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Add) 7.4.1.6.1 The provisions of 7.4.1.6 shall not apply to buildings for which a building permit was issued prior to June 15, 1994.
(Amd) 7.7.2 Discharge through Areas on Level of Exit Discharge. Not more than 50 per cent of the required number of exits, and not more than 50 per cent of the required egress capacity, shall be permitted to discharge through areas on the level of exit discharge, unless otherwise permitted in 7.7.2.1 and 7.7.2.2, provided that the criteria of 7.7.2.3 through 7.7.2.7 are met.
(Amd) 7.9.1.1* Emergency lighting facilities for means of egress shall be provided in accordance with 7.9 for the following:
(Del) 7.9.3 Delete section.
Chapter 8
Features of Fire Protection
(Amd) Table 8.3.4.2 Minimum Fire Protection Ratings for Opening Protectives in Fire Resistance-Rating Assemblies
Component | Walls and Partitions (hr) | Fire Door Assemblies (hr) | Fire Window Assemblies (hr) |
Elevator hoistways | 2 | 11/2 | NP |
1 | 1 | NP | |
Vertical shafts (including stairways, exits, and refuse chutes) | 2 | 11/2 | NP |
1 | 1 | NP (3/4 in other than exits) NP (1/3 in other than exits | |
1/2 | 1/2 | ||
Fire barriers | 2 | 11/2 | NP |
1 | 3/4 | 3/4 | |
Horizontal exits | 2 | 11/2 | NP |
Exit access corridors1 | 1 | 1/3 | 3/4 |
1/2 | 1/3 | 1/3 | |
Smoke barriers1 | 1/2 | 1/3 | 3/4 |
Smoke partitions1,2 | 1/2 | 1/3 | 1/3 |
Note: NP = not permitted. 1Fire doors are not required to have a hose stream test per NFPA 252. 2For residential board and care, see 33.2.3.1.1. |
(Add) 8.3.4.3.1
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Amd) 8.6.7* Atriums. Unless prohibited by Chapter 12 through Chapter 42, an atrium shall be permitted provided the following conditions are met:
(Amd) 8.6.8.2 Where permitted by Chapter 12 through Chapter 42, unenclosed vertical openings not concealed within the building construction shall be permitted as follows:
(Amd) 8.6.9.3 Openness. Mezzanines shall be in accordance with either 8.6.9.3.1, 8.6.9.3.2, 8.6.9.3.3, 8.6.9.3.4 or 8.6.9.3.5.
(Add) 8.6.9.3.3 A mezzanine or portions thereof are not required to be open to the room in which the mezzanines are located, provided that the aggregate floor area of the enclosed space does not exceed 10 per cent of the mezzanine area.
(Add) 8.6.9.3.4 In industrial facilities, mezzanines used for control equipment are permitted to be glazed on all sides.
(Add) 8.6.9.3.5 In industrial occupancies permitted to be of unlimited area by the State Building Code, mezzanines or portions thereof are not required to be open to the room in which the mezzanines are located, provided that an approved fire alarm system is installed throughout the entire building or structure and notification appliances are installed throughout the mezzanines in accordance with the provisions of NFPA 72®. In addition, the fire alarm system shall be initiated by automatic sprinkler water flow.
(Amd) 8.7.3.1 The storage and handling of flammable liquids or gases shall be in accordance with the following applicable codes:
Chapter 9
Building Service and Fire Protection Equipment
(Amd) 9.1.1 Gas. Equipment utilizing gas and related gas piping shall be installed in accordance with the Connecticut Gas Equipment and Piping Code or the Connecticut Liquefied Petroleum Gas and Liquefied Natural Gas Code, unless such installations are approved existing installations, which shall be permitted to be continued in service.
(Amd) 9.2.2 Ventilating or heat-producing equipment shall be installed in accordance with NFPA 91, Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Non-combustible Particulate Solids; NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances; the Connecticut Oil Burning Equipment Code; the Connecticut Gas Equipment and Piping Code; or NFPA 70, National Electrical Code®, as applicable unless such installations are approved existing installations, which shall be permitted to be continued in service.
(Amd) 9.4.2.1 New and existing elevators, escalators, dumbwaiters, and moving walks shall be installed and maintained in accordance with the requirements of the Connecticut Safety Code for Elevators and Escalators enforced by the Connecticut Department of Public Safety.
(Del) 9.4.2.2 Delete section.
(Del) 9.4.3 Delete section.
(Del) 9.4.5* Delete section.
(Del) 9.4.6 Delete section.
(Amd) 9.6.2.10.2 Smoke alarms shall receive their operating power as follows:
(Add) 9.6.3.5.7 When selective occupant notification is utilized in accordance with 9.6.3.6.2 or 9.6.3.6.3, the portions of the building that do not receive the initial notification of alarm shall be separated from areas of the immediate emergency and initial evacuation by construction having a fire resistance rating of at least 1 hour.
(Amd) 9.7.1.2
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Add) 9.7.1.5 Statutory Requirements.
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Add) 9.7.1.6 Buildings provided with standby electrical power for the purpose of continuing operations or occupancy shall provide standby power for any electric fire pump installed to provide an adequate water supply or minimum operating pressure to a required automatic sprinkler system, except that existing installations may be continued in service subject to the approval of the authority having jurisdiction.
Standby power in accordance with NFPA 70, National Electrical Code®, and NFPA 110, Standard for Emergency and Standby Power Systems, Type 60 shall be provided. The standby power system shall have a capacity and rating sufficient to supply all required equipment. Selective load pickup and load shedding shall be permitted in accordance with NFPA 70, National Electrical Code®.
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
Chapter 10
Interior Finish, Contents, and Furnishings
(Amd) 10.2.4.1* Textile Wall and Textile Ceiling Materials. The use of textile materials on walls or ceilings shall comply with one of the following conditions:
(Amd) 10.2.4.2* Expanded Vinyl Wall or Ceiling Coverings. The use of expanded vinyl wall or ceiling coverings shall comply with one of the following conditions:
Chapter 11
Special Structures and High-Rise Buildings
(Amd) 11.7.3.4 Underground and limited access structures, and all areas and floor levels traversed in traveling to the exit discharge, shall be protected by an approved, supervised automatic sprinkler system in accordance with 9.7, unless such structures meet one of the following criteria:
(Del) 11.9.1.6.3 Delete section.
(Del) 11.10 Temporary Membrane Structures. Delete section.
(Del) 11.11 Tents. Delete section.
Chapter 12
New Assembly Occupancies
(Del) Delete Chapter.
Chapter 13
Existing Assembly Occupancies
(Del) 13.1.1.2 Delete section.
(Del) 13.1.1.4 Delete section.
(Del) 13.1.1.5 Delete section.
(Del) 13.1.6 Delete section.
(Amd) Table 13.2.3.2 Capacity Factors
No. of Seats | Clear Width per Seat Served | |||
Stairs | Passageways, Ramps, and Doorways | |||
Mm | in. | mm | in. | |
Unlimited | 7.6 AB | 0.3 AB | 5.6 C | 0.22 C |
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Amd) 13.2.5.1.1 The common paths of travel shall be permitted for the first 9144 mm (360 in.) from any point where the common path serves any number of occupants, and for the first 23 m (75 ft) from any point where the common path serves not more than 50 occupants.
(Amd) 13.2.5.1.2 Dead-end corridors shall not exceed 6100 mm (240 in.), except that a dead-end corridor shall not be limited in length where the length of the dead-end corridor is less than 2.5 times the least width of the dead-end corridor.
(Amd) 13.2.5.6.3* Minimum Aisle Width. The minimum clear width of aisles shall be sufficient to provide egress capacity in accordance with 13.2.3.2 but shall not be less than the following:
(Amd) 13.2.11.1 Guards and Railings: Boxes, Balconies, and Galleries. Boxes, balconies and galleries shall meet the following criteria:
(Amd) 13.3.2.1.2
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Amd) 13.3.3.4 Screens on which pictures are projected shall comply with the requirements of Class A or Class B interior finish in accordance with 10.2 or NFPA 701 in accordance with 10.3.1, as applicable.
(Amd) 13.3.4.3.4 The announcement shall be made via an approved voice communication or public address system that is provided with an emergency power source and that is audible above the ambient noise level of the assembly occupancy.
(Add) 13.3.5.4 Buildings with occupant loads greater than 300 for which a building permit for new occupancy was issued on or after April 15, 1987 shall be protected by an approved supervised automatic sprinkler system in accordance with section 9.7.1 as follows:
(Add) 13.3.5.5 The requirements of 13.3.5.4 shall not apply to the following:
(Add) 13.3.5.6 Automatic sprinkler protection shall also be provided as required by 9.7.1.5.
(Amd) 13.3.6 Corridors. Interior corridors and lobbies shall be separated from use areas by fire barriers having a fire resistance rating of not less than 1 hour in accordance with 8.3, except under any of the following conditions:
(Amd) 13.4.5.7.6 This requirement shall not apply to proscenium fire curtains or water curtains complying with 13.4.5.7.6.1 through 13.4.5.7.6.3.
(Add) 13.4.5.7.6.1* Proscenium Opening Protection. The proscenium opening shall be protected by a fire curtain or an approved water curtain complying with NFPA 13, Standard for the Installation of Sprinkler Systems.
(Add) 13.4.5.7.6.2 The fire curtain or water curtain shall be designed to activate upon automatic detection of a fire and upon manual activation.
(Add) 13.4.5.7.6.3
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Amd) 13.4.5.12.1 Stages over 93 m2 (1000 ft2) in area shall be equipped with 38-mm (11/2-in.) hose connections for first aid fire fighting at each side of the stage.
(Amd) 13.4.8.3.2 An outdoor wooden grandstand unit shall not exceed 929 m2 (10,000 ft2) in ground area or 61 m (200 ft) in length, and the following requirements also shall apply:
(Del) 13.7 Operating Features. Delete section.
Chapter 14
New Educational Occupancies
(Del) Delete Chapter.
Chapter 15
Existing Educational Occupancies
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Add) 15.2.2.2.3.1 Access-controlled egress doors complying with 7.2.1.6.2 shall be permitted in the means of egress on the entrance doors to buildings and to tenant spaces. These doors shall not be secured from the egress side when the occupancy is open to the general public.
(Amd) 15.2.3.2 Minimum Corridor Width. Exit access corridors shall have not less than 1830 mm (72 in.) of clear width, unless they serve an occupancy of 100 or less, then the exit access corridors shall have not less than 1120 mm (44 in.) of clear width.
(Amd) 15.2.4 Number of Exits. Not less than two separate exits shall be as follows, except as permitted by 15.2.4.1:
(Add) 15.2.4.1 A one-story educational occupancy shall be permitted to have a single exit provided the occupancy has a maximum of 50 occupants and a maximum travel distance of 23 m (75 ft) to the exit.
(Amd) 15.2.5.2 No dead-end corridor shall exceed 6100 mm (240 in.), other than in buildings protected throughout by an approved, supervised, automatic sprinkler system in accordance with 9.7, in which case dead-end corridors shall not exceed 15 m (50 ft), or that a dead-end corridor shall not be limited in length where the length of the dead-end corridor is less than 2.5 times the least width of the dead-end corridor.
(Amd) 15.2.9.1 Emergency lighting shall be provided in accordance with section 7.9 unless otherwise permitted by either 15.2.9.2 or 15.2.9.3.
(Add) 15.2.9.3 Educational occupancies permitted to have a single means of egress in accordance with 15.2.4.1 shall not be required to have emergency lighting.
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Amd) 15.2.11.1.2
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Amd) 15.3.2.1
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Amd) 15.3.5.3 Automatic sprinkler protection shall not be required where student occupancy exists below the level of exit discharge, provided that either of the following criteria are met:
(1) Where every classroom has at least one exterior exit door at ground level.
(2) Windows for rescue and ventilation shall be provided in accordance with 15.2.11.1.
(Add) 15.3.5.6 Automatic sprinkler protection shall also be provided as required by 9.7.1.5.
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Add) 15.3.6.1 Self-closing devices may be omitted on doors between corridors and classrooms, except rooms or areas used as shops or laboratories, where the facility has a written and practiced fire exit drill policy which provides for the closing of all corridor doors upon evacuation, and where said policy provides for doors to classrooms not in use to be kept closed.
(Del) 15.7 Operating Features. Delete section.
Chapter 16
New Day-Care Occupancies
(Del) Delete Chapter.
Chapter 17
Existing Day-Care Occupancies
(Amd) 17.1.1.2 The requirements of 17.1 through 17.5 and 17.7 shall apply to existing day-care occupancies in which more than 12 clients receive care, maintenance, and supervision by other than their relative(s) or legal guardian(s) for less than 24 hours per day. An existing day-care occupancy shall be permitted the option of meeting the requirements of Part III of this code in accordance with section 29-292-11e in lieu of Chapter 17. An existing day-care occupancy that meets the requirements of Part III shall be judged as meeting the requirements of Chapter 17.
(Amd) 17.1.1.3 The requirements of 17.1 (other than 17.1.6) and 17.4 through 17.7 shall apply to existing day-care homes as defined in 17.1.3. An existing day-care home shall be permitted the option of meeting the requirements of Part III of this code in accordance with section 29-292-11e in lieu of Chapter 17. An existing daycare home that meets the requirements of Part III shall be judged as meeting the requirements of Chapter 17.
(Amd) 17.1.4.3* Conversions. A conversion from a day-care home to a day-care occupancy with more than 12 clients shall be permitted only if the day-care occupancy conforms to the requirements of Part III of this code in accordance with section 29-292-11e.
(Amd) Table 17.1.6 Location and Construction Type Limitations
Location of Day-Care Occupancy | Sprinklered Building | Construction Type |
1 story below LED | Yes | I(443), I(332), II(222), II(111), II(000), III(211), IV(2HH), V(111) |
No | I(443), I(332), II(222), II(111), III(211), IV(2HH), V(111) | |
Level of exit discharge | Yes | Any type |
No | Any type | |
1 story above LED | Yes | Any type |
No | I(443), I(332), II(222) | |
No | II(111)*, III(211)*, V(111)* | |
2 stories above LED | Yes | I(443), I(332), II(222) |
Yes | II(111)*, III(211)*, V(111)* | |
No | I(443), I(332), II(222) | |
[GREATER THAN OR EQUAL TO]3 stories above LED but not high-rise | Yes | I(443), I(332), II(222) |
Yes | II(111)* | |
No | I(443), I(332), II(222) | |
High-rise | Yes | I(443), I(332), II(222) |
No | Not permitted | |
LED: Level of exit discharge. *Permitted only if clients capable of self-preservation. |
(Add) 17.2.2.2.3.1 Access-controlled egress doors complying with 7.2.1.6.2 shall be permitted in the means of egress on the entrance doors to buildings and to tenant spaces. These doors shall not be secured from the egress side when the occupancy is open to the general public.
(Amd) 17.2.5.2 No dead-end corridor shall exceed 6100 mm (240 in.), other than in buildings protected throughout by an approved, supervised, automatic sprinkler system in accordance with 9.7, in which case dead-end corridors shall not exceed 15 m (50 ft), or that a dead-end corridor shall not be limited in length where the length of the dead-end corridor is less than 2.5 times the least width of the dead-end corridor.
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Amd) 17.3.2.1
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Add) 17.3.5.4 Automatic sprinkler protection shall also be provided as required by 9.7.1.5.
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Add) 17.3.6.1 Self-closing devices may be omitted on doors between corridors and client activity rooms where the facility has a written and practiced fire exit drill policy which provides for the closing of all corridor doors upon evacuation, and where said policy provides for doors to client activity rooms not in use to be kept closed.
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Add) 17.6.1.1.6 The requirements of 17.6 shall not apply to facilities located within residential living units or private dwellings and providing care, maintenance and supervision to not more than six children except that during the school year a maximum of three additional children who are in school full time shall be permitted for up to three hours before school and up to three hours after school. Such facilities are subject to the regulations adopted by the Connecticut Department of Public Health and are exempt from the requirements of this code.
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Del) 17.6.1.7 Delete section.
(Del) 17.7 Operating Features. Delete section.
Chapter 18
New Health Care Occupancies
(Del) Delete Chapter.
Chapter 19
Existing Health Care Occupancies
(Amd) 19.1.1.1.1* The requirements of this chapter shall apply to existing buildings or portions thereof currently occupied as health care occupancies, unless the State Fire Marshal has determined equivalent safety has been provided in accordance with 1.4.
(Del) 19.1.1.4 Additions, Conversions, Modernizations, Renovation, and Construction Operations. Delete section.
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Amd) 19.2.2.5.4 Door openings in horizontal exits shall be protected by one of the following methods:
(Amd) 19.2.4.1 Not less than two exits of the types described in 19.2.2.2 through 19.2.2.10, remotely located from each other, shall be provided for each floor or fire section of the building, except that a single exit shall be permitted for a one-story building with a maximum occupant load of 10 persons and a maximum travel distance of 23 m (75 ft) to the exit.
(Amd) 19.2.5.10* Existing dead-end corridors shall be permitted to continue in use if it is impractical and unfeasible to alter them so that exits are accessible in not less than two different directions from all points in aisles, passageways and corridors. A dead-end corridor shall not be limited in length where the length of the dead-end corridor is less than 2.5 times the least width of the dead-end corridor.
(Amd) 19.2.9.1 Emergency lighting shall be provided in accordance with 7.9 unless otherwise permitted by 19.2.9.2.
(Add) 19.2.9.2 Health care occupancies permitted to have a single means of egress in accordance with section 19.2.4.1 shall not be required to have emergency lighting.
(Amd) 19.3.2.1.5
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Add) 19.3.5.1.1 Automatic sprinkler protection shall also be provided as required by 9.7.1.5.
(Del) 19.3.5.7 Delete section.
(Amd) 19.3.6.5.2 The alternative requirements of 19.3.6.5.1 shall not apply where otherwise modified by the following:
(Del) 19.7 Operating Features. Delete section.
Chapter 20
New Ambulatory Health Care Occupancies
(Del) Delete Chapter.
Chapter 21
Existing Ambulatory Health Care Occupancies
(Del) 21.1.1.4 Additions, Conversions, Modernizations, Renovation, and Construction Operations. Delete section.
(Del) 21.1.6.7 Delete section.
(Add) 21.2.2.2.1 Access-controlled egress doors complying with 7.2.1.6.2 shall be permitted in the means of egress on the entrance doors to buildings and to tenant spaces. These doors shall not be secured from the egress side when the occupancy is open to the general public.
(Amd) 21.2.4.1 Not less than two exits of the types described in 39.2.2 that are remotely located from each other shall be provided for each floor or fire section of the building, except that a single exit shall be permitted for a one-story building with a maximum occupant load of 10 persons and a maximum travel distance of 23 m (75 ft) to the exit.
(Amd) 21.2.9.1 Emergency lighting shall be provided in accordance with 7.9 unless otherwise permitted by 21.2.9.1.1.
(Add) 21.2.9.1.1 Ambulatory health care occupancies permitted to have a single means of egress in accordance with 21.2.4.1 shall not be required to have emergency lighting.
(Del) 21.3.5.3 Delete section.
(Del) 21.7 Operating Features. Delete section.
Chapter 22
New Detention and Correctional Occupancies
(Del) Delete Chapter.
Chapter 23
Existing Detention and Correctional Occupancies
(Amd) 23.2.5.2* Existing dead-end corridors greater than 15 m (50 ft) are undesirable and shall be altered wherever possible so that exits are accessible in not less than two different directions from all points in aisles, passageways and corridors. A dead-end corridor shall not be limited in length where the length of the dead-end corridor is less than 2.5 times the least width of the dead-end corridor.
(Add) 23.3.2.1.1 The protection requirements of Table 23.3.2.1 shall apply to those boiler and fuel-fired heater rooms where any piece of equipment is over 400,000 Btu per hour input.
(Add) 23.3.5.1.1 Automatic sprinkler protection shall also be provided as required by 9.7.1.5.
(Del) 23.3.5.4 Delete section.
(Del) 23.7 Operating Features. Delete section.
Chapter 24
One- and Two-Family Dwellings
(Amd) 24.1.1.1* The requirements of this chapter shall apply to existing one- and two-family dwellings, which shall include those buildings containing not more than two dwelling units in which each dwelling unit is occupied by members of a single family with not more than six outsiders, if any, accommodated in rented rooms, except those occupancies classified as health care, residential board and care or detention and correctional.
Buildings which contain a maximum of two dwelling units and no other occupancies are specifically exempted by section 29-292 of the Connecticut General Statutes from the jurisdiction of this code, except for the specific smoke detection provisions set forth in 24.3.4.
(Amd) 24.1.2.2 No dwelling unit may have its sole means of escape through another dwelling unit or other occupancy.
(Add) 24.1.2.2.1 Where one or two dwelling units are present in a building containing another occupancy, each dwelling shall be provided with a primary means of escape in accordance with 24.2.2.2. If the primary means of escape consists of an interior stairway, the stairway shall be separated by at least 1/2-hour fire barriers with all openings protected by self-closing doors of an equivalent rating.
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Amd) 24.3.4.3 Residential buildings designed to be occupied by one family for which a building permit for new occupancy was issued prior to October 1, 1978 are not required to comply with 24.3.4.
Chapter 25
Reserved
Chapter 26
Lodging or Rooming Houses and Bed and Breakfasts
(Amd) 26.1.1.1* The requirements of this chapter shall apply to existing buildings or portions thereof that do not qualify as a one- or two-family dwelling that provide sleeping accommodations for a total of 16 or fewer persons on either a transient or permanent basis, with or without meals, but without separate cooking facilities for individual occupants except as provided in Chapter 24.
(Amd) 26.2.2.2 Where an interior stair connects the street floor with the story next above or below only, but not with both, the interior stair shall be required to be enclosed only on the street floor. In bed and breakfasts, this exception shall not apply to stairs below the street floor.
(Add) 26.2.3.7 Access-controlled egress doors complying with 7.2.1.6.2 shall be permitted in the means of egress on the entrance doors to buildings and to tenant spaces.
(Add) 26.2.4 Illumination. The primary means of escape within bed and breakfasts shall be provided with illumination in accordance with 7.8, unless illumination is provided upon activation of the fire alarm system or loss of power. The foot-candle values of illumination provided shall be as required by 7.9.2.1.
(Add) 26.3.1.1.4 In existing lodging or rooming houses, two or fewer stories in height, and in bed and breakfasts, stair enclosures shall not be required for levels at and above the street floor level when the building is provided with an approved household fire warning system in accordance with the requirements of NFPA 72®, National Fire Alarm Code®. This system shall consist of a control unit with smoke detectors, a manual fire alarm box on each floor level, and occupant notification with a heat detector installed in the kitchen. The kitchen shall also be separated by 1/2-hour fire-resistive construction, or shall be protected by a limited area sprinkler system, or the range top shall be protected by a listed residential range top extinguisher unit.
(Amd) 26.3.3.5.3 Each lodging or rooming house shall install a smoke alarm which, when activated, shall provide an approved visible alarm suitable to warn occupants in at least one room.
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Add) 26.3.5.4 Automatic sprinkler protection shall also be provided as required by 9.7.1.5.
(Add) 26.3.5.5 Portable fire extinguishers shall be required only in kitchens of bed and breakfasts. These portable fire extinguishers shall be installed and maintained in accordance with 9.7.4.1, unless the range top is protected by a listed residential range top extinguisher unit.
Chapter 27
Reserved
Chapter 28
New Hotels and Dormitories
(Del) Delete Chapter.
Chapter 29
Existing Hotels and Motels
(Amd) 29.1.1.1 The requirements of this chapter shall apply to existing buildings or portions thereof currently occupied as hotel or motel occupancies.
(Del) 29.1.1.2 Delete section.
(Amd) 29.1.3 Definitions. Terms applicable to this chapter are defined in Chapter 3 of this code and include the terms in the list that follows:
(Add) 29.2.2.2.3.1 Access-controlled egress doors complying with 7.2.1.6.2 shall be permitted in the means of egress on the entrance doors to buildings and to tenant spaces.
(Amd) 29.2.4.1 In buildings other than those complying with 29.2.4.2, not less than two exits shall be provided from every floor, including floors below the level of exit discharge and occupied for public purposes.
(Amd) 29.2.4.2 Buildings of four stories or less protected throughout by an approved, supervised automatic sprinkler system in accordance with 29.3.5, with not more than four guest rooms or guest suites per floor, shall be permitted to have a single exit under the following conditions:
(Amd) 29.2.5.5 Dead-end corridors shall not exceed 50 ft (15 m), except that a dead-end corridor shall not be limited in length where the length of the dead-end corridor is less than 2.5 times the least width of the dead-end corridor.
(Amd) 29.3.2.2.2 The areas described in Table 29.3.2.2.2 shall be protected as indicated, except that residential-type heating appliances such as domestic hot water heaters, domestic furnaces or domestic boilers may be unenclosed when located within an individual guest room or suite serving only that room or suite that is separated from all adjacent rooms or suites by construction having at least a 1/2-hour fire resistance rating.
(Amd) Table 29.3.2.2.2 Hazardous Area Protection
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Amd) 29.3.4.4 Detection.
(Add) 29.3.4.4.1 A corridor smoke detection system in accordance with 9.6 shall be provided, unless otherwise permitted by either of the following:
(Del) 29.3.4.5.1
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Del) 29.3.4.5.2 Delete section.
(Amd) 29.3.5.1 An approved, supervised automatic sprinkler system shall be provided as required by 9.7.1.5.
(Del) 29.3.5.7 Delete section.
(Amd) 29.3.6.7 Transoms, louvers or transfer grilles shall be prohibited in walls or doors of exit access corridors, unless meeting 29.3.6.7.1.
(Del) 29.3.6.7.2 Delete section.
(Del) 29.3.6.7.3 Delete section.
(Del) 29.7 Operating Features. Delete section.
Chapter 30
New Apartment Buildings
(Del) Delete Chapter.
Chapter 31
Existing Apartment and Dormitory Buildings
(Amd) 31.1.1.1 The requirements of this chapter shall apply to existing buildings or portions thereof currently occupied as apartment or dormitory occupancies. In addition, the building shall meet the requirements of one of the following options:
(Add) 31.1.1.3 All buildings containing three or more individual living units shall be classified as apartment buildings, except where the building and living unit arrangement is in accordance with items numbered (1) through (4) of this section, then the entire building shall be exempt from the requirements of this chapter and the individual living units need only comply with the requirements for smoke alarms in 31.3.4.5 and each living unit shall be treated as a single family home for the purposes of section 29-305 of the Connecticut General Statutes:
(Amd) 31.1.2.3 Multiple dwelling units shall be permitted to be located above a nonresidential occupancy only where one of the following conditions exists:
(Add) 31.1.3.3 Dormitory. See 3.3.48.
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Add) 31.2.2.2.3.1 Access-controlled egress doors complying with 7.2.1.6.2 shall be permitted in the means of egress on the entrance doors to buildings and to tenant spaces.
(Amd) 31.2.4.2 Any dwelling unit shall be permitted to have a single exit, provided that one of the following criteria is met:
(Amd) 31.2.4.3 Any building of four stories or less protected throughout by an approved, supervised automatic sprinkler system in accordance with 31.3.5.3 shall be permitted to have a single exit, provided the following conditions are met:
(Amd) 31.2.4.4 Any building of three stories or less in its entirety shall be permitted to have a single exit, provided the following conditions are met:
(Amd) 31.2.5.4 Dead-end corridors shall not exceed 15 m (50 ft), except that a dead-end corridor shall not be limited in length where the length of the dead-end corridor is less than 2.5 times the least width of the dead-end corridor.
(Add) 31.3.2.1.1.1 Residential-type heating appliances such as domestic hot water heaters, domestic furnaces or domestic boilers may be unenclosed when located within an individual living unit and serving that living unit only.
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Add) 31.3.2.1.1.2
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Del) 31.3.4.3.5 Delete section.
(Amd) 31.3.4.5.1 Approved single-station smoke alarms shall be installed in accordance with 9.6.2.10, outside every sleeping area in the immediate vicinity of the bedrooms and on all levels of the dwelling unit, including basements.
(Del) 31.3.4.5.2 Delete section.
(Amd) 31.3.5.6 Buildings using Option 3 shall be provided with the following:
(1) Automatic sprinklers in the corridor along the corridor ceiling.
(2) An automatic sprinkler within any dwelling unit that opens into the corridor, with such sprinkler positioned over the center of the door.
(Amd) 31.3.5.10 All high-rise buildings as required by 9.7.1.5, shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with 31.3.5.3.
(Del) 31.3.5.10.1 Delete section.
(Del) 31.3.5.10.2 Delete section.
(Del) 31.3.5.10.3 Delete section.
(Del) 31.3.5.11 Delete section.
(Amd) 31.3.6.6 Spaces shall be permitted to be unlimited in area and open to the corridor, provided that the following criteria are met:
(Del) 31.7 Operating Features. Delete section.
Chapter 32
New Residential Board and Care Occupancies
(Del) Delete Chapter.
Chapter 33
Existing Residential Board and Care Occupancies
(Del) 33.1.1.2* Delete section.
(Del) 33.1.1.4 Conversion. Delete section.
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Add) 33.2.2.4.8 Stairs shall be permitted to be open at the topmost story only where all of the following are met:
(Amd) 33.2.2.5.6.1 Delayed egress locks complying with 7.2.1.6.1 shall be permitted. A building occupant shall not be required to pass through more than one door equipped with a delayed egress lock before entering an exit.
(Add) 33.2.2.5.6.2 Access-controlled egress doors complying with 7.2.1.6.2 shall be permitted in the means of egress on the entrance doors to buildings and to tenant spaces.
(Amd) 33.2.3.4.3.1 Approved smoke alarms shall be provided in accordance with 9.6.2.10.
(Del) 33.2.3.4.3.5 Delete section.
(Del) 33.2.3.4.3.6 Delete section.
(Add) 33.3.2.2.2.1 Where permitted by 33.3.2.2.2, access-controlled egress doors complying with 7.2.1.6.2 shall be permitted in the means of egress on the entrance doors to buildings and to tenant spaces.
(Amd) 33.3.2.5.4 Dead-end corridors shall not exceed 15 m (50 ft), except that a dead-end corridor shall not be limited in length where the length of the dead-end corridor is less than 2.5 times the least width of the dead-end corridor.
(Amd) 33.3.2.6.2 Travel distance from the door within a room, suite, or living unit to a corridor door shall not exceed 38 m (125 ft) in buildings protected throughout by an approved automatic sprinkler system in accordance with 33.3.3.5.
(Amd) 33.3.3.2.2
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Amd) 33.3.3.4.7 Smoke Alarms. Smoke alarms shall be provided in accordance with 33.3.3.4.7.1.
(Del) 33.3.3.4.7.2 Delete section.
(Del) 33.3.3.4.7.3 Delete section.
(Add) 33.3.3.5.2.1 Automatic sprinkler protection installed in accordance with 33.3.3.5 shall also be provided as required by 9.7.1.5.
(Del) 33.3.3.5.6 Delete section.
(Del) 33.7 Operating Features. Delete section.
Chapter 34
Reserved
Chapter 35
Reserved
Chapter 36
New Mercantile Occupancies
(Del) Delete Chapter.
Chapter 37
Existing Mercantile Occupancies
(Amd) 37.1.2.2.1 The fire barrier separating parking structures from a building classified as a mercantile occupancy shall be a fire barrier having a fire resistance rating of not less than 2 hours, or 1 hour when both structures are protected throughout by an automatic sprinkler system in accordance with 9.7.1.1(1).
(Amd) 37.2.2.2.5 Access-controlled egress doors complying with 7.2.1.6.2 shall be permitted in the means of egress on the entrance doors to buildings and to tenant spaces. The entrance doors shall not be secured from the egress side when the occupancy is open to the general public.
(Amd) 37.2.4 Number of Exits.
(Add) 37.2.4.1
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Add) 37.2.4.2 Exit access required by 37.2.4.1(3) shall be permitted to include a single exit access path for the distances permitted as common paths of travel by 37.2.5.3.
(Add) 37.2.4.3 A single means of egress shall be permitted in a Class C mercantile occupancy, provided the travel distance to the exit or to a mall does not exceed 23 m (75 ft).
(Add) 37.2.4.4 A single means of egress shall be permitted in a Class C mercantile occupancy, provided the travel distance to the exit or to a mall does not exceed 30 m (100 ft), and the story on which the occupancy is located and all communicating levels that are traversed to reach the exit or mall are protected throughout by an approved, supervised automatic sprinkler system in accordance with 9.7.1.1(1).
(Add) 37.2.4.5 A single means of egress to an exit or to a mall shall be permitted from a mezzanine within any Class A, Class B or Class C mercantile occupancy, provided that the common path of travel does not exceed 23 m (75 ft), or does not exceed 30 m (100 ft) if protected throughout by an approved, supervised automatic sprinkler system in accordance with 9.7.1.1(1).
(Add) 37.2.4.6 A single exit shall be permitted for a maximum two-story single tenant space/building that has a maximum area per floor of 160 m2 (1,500 ft2) and is protected throughout by an automatic fire detection system that includes smoke detection in all occupied spaces and heat detection in hazardous and unoccupied areas. Each occupied room on the second floor of the space/building shall be provided with a secondary means of escape in accordance with 24.2.2.3. The total travel to the outside shall not exceed 23 m (75 ft).
(Amd) 37.2.5.2* Dead-end corridors shall not exceed 15 m (50 ft), except that a dead-end corridor shall not be limited in length where the length of the dead-end corridor is less than 2.5 times the least width of the dead-end corridor.
(Amd) 37.2.6.2 In buildings not complying with 37.2.6.1, the travel distance shall not exceed 61 m (200 ft).
(Amd) 37.3.2.1.1
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Amd) 37.3.3.2.1 Interior wall and ceiling finish materials complying with 10.2 shall be Class A or B. Class C interior finish materials shall be permitted within rooms and spaces enclosed by partitions.
(Amd) 37.3.5.2 Automatic sprinkler protection shall also be provided as required by 9.7.1.5.
(Del) 37.3.5.3 Delete section.
(Amd) 37.3.6 Corridors. Where access to exits is limited to corridors, such corridors shall be separated from use areas by fire barriers having a fire resistance rating of not less than 1 hour in accordance with 8.3, except under any of the following conditions:
(Amd) 37.4.4.4.1 General. Mall buildings shall be provided with a fire alarm system in accordance with 9.6.
(Amd) 37.4.4.4.3.1 Occupant Notification. During all times that the mall building is occupied, the required fire alarm system, once initiated, shall perform one of the following:
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Del) 37.4.5.6 Delete section.
(Del) 37.7 Operating Features. Delete section.
Chapter 38
New B
(Del) Delete Chausiness Occupanciespter.
Chapter 39
Existing Business Occupancies
(Amd) 39.1.2.2.1 The fire barrier separating parking structures from a building classified as a business occupancy shall be a fire barrier having a fire resistance rating of not less than 2 hours, or 1 hour when both structures are protected throughout by an automatic sprinkler system in accordance with 9.7.1.1(1).
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Amd) 39.2.2.2.5 Access-controlled egress doors complying with 7.2.1.6.2 shall be permitted in the means of egress on the entrance doors to buildings and to tenant spaces. The entrance doors shall not be secured from the egress side when the occupancy is open to the general public.
(Amd) 39.2.4.1
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Amd) 39.2.4.2 Exit access as required by 39.2.4.1(3) shall be permitted to include a single exit access path for the distances permitted for common paths of travel by 39.2.5.3.
(Add) 39.2.4.3 A single exit shall be permitted for a room or area with a total occupant load of fewer than 100 persons, provided that the following criteria are met:
(Add) 39.2.4.4 Any business occupancy not exceeding three stories, and not exceeding an occupant load of 30 people per floor, shall be permitted a single separate exit to each floor, provided the following criteria are met:
(Add) 39.2.4.5 A single means of egress shall be permitted from a mezzanine within a business occupancy, provided that the common path of travel does not exceed 23 m (75 ft), or 30 m (100 ft) if protected throughout by an approved automatic sprinkler system installed in accordance with 9.7.1.1(1).
(Add) 39.2.4.6 A single exit shall be permitted for a maximum two-story single tenant space/building that is protected throughout by an approved automatic sprinkler system installed in accordance with 9.7.1.1(1) and where the total travel to the outside does not exceed 30 m (100 ft).
(Add) 39.2.4.7 A single exit shall be permitted for a maximum two-story single tenant space/building that has a maximum area per floor of 160 m2 (1,500 ft2) and is protected throughout by an automatic fire detection system that includes smoke detection in all occupied spaces and heat detection in hazardous and unoccupied areas. Each occupied room on the second floor of the space/building shall be provided with a secondary means of escape in accordance with 24.2.2.3. The total travel to the outside shall not exceed 23 m (75 ft).
(Amd) 39.2.5.2* Dead-end corridors shall not exceed 15 m (50 ft), except that a dead-end corridor shall not be limited in length where the length of the dead-end corridor is less than 2.5 times the least width of the dead-end corridor.
(Amd) 39.3.2.1*
See the 2009 Amendment to the 2005 CT State Fire Safety Code.
(Amd) 39.3.5.1 Extinguishment Requirements. Automatic sprinkler protection shall also be provided as required by 9.7.1.5.
(Amd) 39.3.6. Corridors. Where access to exits is limited to corridors, such corridors shall be separated from use areas by fire barriers having a fire resistance rating of not less than 1 hour in accordance with 8.3, except under any of the following conditions:
Openings in corridor partitions required to have a fire resistance rating shall be protected in accordance with 8.3.
(Del) 39.7 Operating Features. Delete section.
Chapter 40
Industrial Occupancies
(Amd) 40.1.1.1 The requirements of this chapter shall apply to existing industrial occupancies. Pursuant to the requirements of section 29-292 of the Connecticut General Statutes, the requirements of this chapter shall not apply to buildings, or portions thereof, utilized for the manufacture of products or goods.
(Amd) 40.2.4.1 The number of means of egress shall comply with either 40.2.4.1.1, 40.2.4.1.2 or 40.2.4.1.3.
(Amd) 40.2.4.1.2 A single means of egress shall be permitted from any story or section in low and ordinary hazard industrial occupancies, provided the following limits are not exceeded:
(Add) 40.2.4.1.3 In low and ordinary hazard industrial occupancies existing prior to May 7, 2000, a single means of egress shall be permitted from any story or section, provided that the exit can be reached within the distance permitted as a common path of travel.
(Amd) 40.2.5 Arrangement of Means of Egress. Means of egress, arranged in accordance with section 7.5, shall not exceed that provided by Table 40.2.5, except that a dead-end corridor shall not be limited in length where the length of the dead-end corridor is less than 2.5 times the least width of the dead-end corridor.
(Amd) 40.3.5 Automatic sprinkler protection shall also be provided as required by 9.7.1.5.
(Amd) 40.4 Special Provisions; High-Rise Buildings. Automatic sprinkler protection shall also be provided as required by 9.7.1.5 and 11.8.2.1.
Chapter 41
Reserved
Chapter 42
Storage Occupancies
(Amd) 42.1.1.1 The requirements of this chapter shall apply to existing storage occupancies.
(Amd) 42.2.4.1 The number of means of egress shall comply with 42.2.4.1(1), 42.2.4.1(2), 42.2.4.1(3) or 42.2.4.1(4).
(Amd) 42.2.5.1 Means of egress, arranged in accordance with 7.5, shall not exceed that provided by Table 42.2.5.1, except that a dead-end corridor shall not be limited in length where the length of the dead-end corridor is less than 2.5 times the least width of the dead-end corridor.
(Amd) 42.2.6* Travel Distance to Exits. Travel distance, measured in accordance with 7.6, shall not exceed that provided by Table 42.2.6, except existing low hazard storage shall have no limits.
(Amd) Table 42.2.6 Maximum Travel Distance to Exits
Level of Protection | Low Hazard Storage Occupancy | Ordinary Hazard Storage Occupancy | High Hazard Storage Occupancy |
Protected throughout by an approved, supervised automatic sprinkler system in accordance with 9.7.1.1(1) | 122 m (400 ft) | 122 m (400 ft) | 30 m (100 ft) |
Not protected throughout by an approved, supervised automatic sprinkler system in accordance with 9.7.1.1(1) | 91 m (300 ft) | 61 m (200 ft) | 23 m (75 ft) |
Flammable and combustible liquid products stored and protected in accordance with NFPA 30, Flammable and Combustible Liquids Code. | Not applicable | Not applicable | 46 m (150 ft) |
(Amd) 42.3.5 Automatic sprinkler protection shall also be provided as required by 9.7.1.5.
(Amd) 42.8.3.5 Automatic sprinkler protection shall also be provided as required by 9.7.1.5.
(Add) 42.8.3.5.1 When open-air parking structures, or open-air facilities are located within mixed occupancy buildings they shall be protected throughout by an approved, automatic sprinkler system when the other occupancy requires such protection throughout the building, unless the provisions of 42.8.3.5.2 are met.
(Add) 42.8.3.5.2 Those portions of a building deemed "open-air parking" shall not be required to be protected by automatic sprinklers if all of the following conditions are met:
Conn. Agencies Regs. § 29-292-21e