where:
G = daily geometric average pollutant concentration, corrected to 7% O2or equivalent percent CO2;
Aj= arithmetic average pollutant concentration, for hour j, corrected to 7% O2or equivalent percent CO2;
n = total number of hourly averages for which pollutant concentrations are available within the 24 hour midnight to midnight daily period;
ln = the natural log function; and
e = the natural logarithmic base (2.718).
Table 38-1. Air Pollutant Emission Limits.
Air pollutant | Emission limit |
Particulate matter | 25 mg/dscm |
Cadmium | 0.035 mg/dscm |
Lead | 0.400 mg/dscm |
Mercury | 0.028 mg/dscm, or 85% reduction by weight measured as required by subsection (c)(7) of this section |
Sulfur dioxide -- Reciprocating grate waste tire fired incinerator/boilers | 51 parts per million by volume (ppmvd), or 75% reduction by weight or volume measured as required by subsection (c)(7) of this section |
Sulfur dioxide -- Mass burn waterwall combustors for which construction commenced after December 20, 1989 | 29 parts per million by volume (ppmvd), or 80% reduction by weight or volume measured as required by subsection (c)(7) of this section |
Sulfur dioxide -- All other MWCs | 29 parts per million by volume (ppmvd), or 75% reduction by weight or volume measured as required by subsection (c)(7) of this section |
Hydrogen chloride | 29 parts per million by volume (ppmvd), or 95% reduction by weight or volume measured as required by subsection (c)(7) of this section |
Hydrogen chloride -- Mass burn waterwall combustors for which construction commenced after December 20, 1989 | 25 parts per million by volume (ppmvd), or 95% reduction by weight or volume measured as required by subsection (c)(7) of this section |
Dioxin/furan | 30 ng/dscm total mass |
Opacity | 10% |
Table 38-2. Nitrogen Oxides Emission Limits.
Municipal waste combustor technology | Nitrogen oxides emission limit, measured in parts per million volume, corrected to seven percent oxygen, dry basis, or equivalent percentage carbon dioxide as specified in subdivision (12) of this subsection |
Mass burn refractory combustor | 177 |
Mass burn waterwall combustor for which construction commenced on or before December 31, 1985 | 200 |
Mass burn waterwall combustor for which construction commenced after December 31, 1985 | 177 |
Processed-municipal solid waste combustor | 146 |
Reciprocating grate waste tire fired incinerator/boiler | 79 |
Table 38-2A. Additional Nitrogen Oxides Emission Limits.
Municipal waste combustor technology | Nitrogen oxides emission limit, measured in parts per million volume, corrected to seven percent oxygen, dry basis, or equivalent percentage carbon dioxide as specified in subdivision (12) of this subsection |
Mass burn refractory combustor | 177 |
Mass burn waterwall combustor | 150 |
Processed-municipal solid waste combustor | 146 |
Reciprocating grate waste tire fired incinerator/boiler | 79 |
Table 38-3. Carbon Monoxide Emission Limits.
Municipal waste combustor technology | Carbon monoxide emission limit, measured in parts per million volume at the combustor outlet and corrected to seven percent oxygen, dry basis, or equivalent percentage carbon dioxide as specified in subdivision (c)(12) of this section | Averaging time, in hours, calculated as an arithmetic average |
Mass burn refractory combustor | 100 | 4 |
Mass burn waterwall combustor | 100 | 4 |
Processed-municipal solid waste combustor | 200 | 24 |
Reciprocating grate waste tire fired incinerator/boiler | 180 | 4 |
Table 38-4. Ammonia Emission Limit.
Air pollutant | Emission limit |
Ammonia | 20 parts per million by volume (ppmvd) at 7% oxygen |
where:
%Phg = percent reduction of the potential mercury emissions achieved.
Ei = potential mercury emission concentration measured at the control device inlet, corrected to 7% O2 (dry basis).
Eo = controlled mercury emission concentration measured at the mercury control device outlet, corrected to 72 (dry basis), and
where:
%PHCl = percent reduction of the potential hydrogen chloride emissions achieved.
Ei = potential hydrogen chloride emission concentration measured at the control device inlet, corrected to 7% O2 (dry basis).
EEo = controlled hydrogen chloride emission concentration measured at the control device outlet, corrected to 7 % O2 (dry basis), and
Conn. Agencies Regs. § 22a-174-38