7 Colo. Code Regs. § 1101-5-5-1

Current through Register Vol. 47, No. 24, December 25, 2024
Section 7 CCR 1101-5-5-1 - Requirement
(a) Any person, firm, partnership, or corporation operating boilers or pressure vessels in Colorado may seek approval and registration as an owner-user inspection organization by filing an application with the Director on the prescribed forms.
(b) The applicant shall show the name of the organization, its principal address in the jurisdiction and the name and address of the person or persons having supervision over inspections made by said organization on the application and registration. The applicant shall report changes in supervisory personnel to the director within 30 days after any such change.
(c) Each owner-user inspection organization shall:
(1) Conduct inspections of its non-exempt boilers, utilizing only qualified owner-user inspectors.
(2) Retain on file at the location where equipment is inspected a true record or copy of the report of each inspection signed by the owner-user inspector who performed the inspection.
(3) Promptly notify the Director of any boiler or pressure vessel that does not meet the requirements for safe operation.
(4) Maintain inspection records that include a list of non-exempt boilers, showing the serial number and such abbreviated description as may be necessary for identification, the date of the last inspection of each unit, the approximate date of the next inspection and documentation of all repairs. Such inspection records shall be readily available for examination by the Director during business hours.
(5) Transmit a statement annually to the Director, on a date mutually agreed upon. Such statement shall be signed by the individual having supervision over the inspections made during the period covered. The statement shall include the number of boilers inspected during the year and shall certify that each inspection was conducted in accordance with the inspection requirements provided by these regulations.
(d) A state-issued certificate of inspection is required for boilers inspected by an owner-user inspection organization when all of the requirements in this Section are met.
(e) An individual or organization performing an inspection pursuant to this Section shall have liability insurance appropriate for the size and scope of the relevant inspection.

7 CCR 1101-5-5-1

40 CR 11, June 10, 2017, effective 7/1/2017