Table 5-Grounding Conductor Size Versus Number of Circuits
Minimum grounding conductor size | Number of circuits | |
Fuseless (carbon or gas tube) | Fused | |
#12 AWG, copper, insulated | 1 to 2 | 1 to 3. |
#10 AWG, copper, insulated | 3 to 5 | 4 to 7. |
#6 AWG, copper, insulated | 6 or more | 8 or more. |
Notes:
7 C.F.R. §1755.508