49 C.F.R. §§ 179.300-17

Current through October 31, 2024
Section 179.300-17 - Tests of pressure relief devices
(a) Each valve shall be tested by air or gas before being put into service. The valve shall open and be vapor-tight at the pressure prescribed in § 179.301 .
(b) Rupture disks of non-reclosing pressure relief devices must be tested and qualified as prescribed in appendix A, Paragraph 5, of the AAR Manual of Standards and Recommended Practices, Section C-Part III, AAR Specifications for Tank Cars (IBR, see § 171.7 of this subchapter).
(c) For pressure relief devices of the fusible plug type, a sample of the plug used shall function at the temperatures prescribed in § 179.300-15 .
(d) The start-to-discharge and vapor-tight pressures shall not be affected by any auxiliary closure or other combination.

49 C.F.R. §§179.300-17

29 FR 18995, Dec. 29, 1964. Redesignated at 32 FR 5606, Apr. 5, 1967, and amended by Amdt. 179-10, 36 FR 21355, Nov. 6, 1971; 66 FR 45390 , Aug. 28, 2001; 68 FR 48572 , Aug. 14, 2003; 68 FR 75763 , Dec. 31, 2003