46 C.F.R. § 196.15-30

Current through November 30, 2024
Section 196.15-30 - Emergency lighting and power systems
(a) Where fitted, it shall be the duty of the master to see that the emergency lighting and power systems are operated and inspected at least once in each week that the vessel is navigated to be assured that the system is in proper operating condition.
(b) Internal combustion engine driven emergency generators shall be operated under load for at least 2 hours, at least once in each month that the vessel is navigated.
(c) Storage batteries for emergency lighting and power systems shall be tested at least once in each 6-month period that the vessel is navigated to demonstrate the ability of the storage battery to supply the emergency loads for the specified period of time.
(d) The date of the tests and the condition and performance of the apparatus shall be noted in the official logbook.

46 C.F.R. § 196.15-30