46 C.F.R. § 194.20-7

Current through November 30, 2024
Section 194.20-7 - Fire protection
(a) Each chemical storeroom must be protected by a fixed automatic extinguishing system using carbon dioxide or a clean agent complying with 46 CFR subpart 95.16, installed in accordance with 46 CFR subpart 193.15.
(b) Portable fire extinguishers are required in accordance with Table 193.50-10(a) of this subchapter.

46 C.F.R. §194.20-7

CGFR 67-83, 33 FR 1151, Jan. 27, 1968, as amended by USCG-2006-24797, 77 FR 33894 , June 7, 2012